Inspection
Inspection Details
Equipment ID
13530
13530
Inspection Date
10/20/2025
10/20/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
365
365
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
19
19
External ID
abf6abab-8ee0-468f-940f-a300cae1125e
abf6abab-8ee0-468f-940f-a300cae1125e
Location
Mallinckrodt Bldg
3600 N 2nd St, St. Louis, MO
Phone: (314) 654-1600
Email: robert.mohr@mnk.com
3600 N 2nd St, St. Louis, MO
Phone: (314) 654-1600
Email: robert.mohr@mnk.com
Owner
Attn: Mallinckrodt
Mallinckrodt
PO Box 982201, El Paso, TX 79998
Phone: (314) 654-1760
Email: robert.mohr@mnk.com
Mallinckrodt
PO Box 982201, El Paso, TX 79998
Phone: (314) 654-1760
Email: robert.mohr@mnk.com
Billing
Attn: Mallinckrodt
Mallinckrodt
3600 N 2nd St, St. Louis, MO 63147
Phone: (314) 654-1760
Email: Ryan.Martin@mnk.com
Mallinckrodt
3600 N 2nd St, St. Louis, MO 63147
Phone: (314) 654-1760
Email: Ryan.Martin@mnk.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post current MO state certificate in machine room | 2/26/2021 |
| conversion | conversion | n/a | No | No | Repair car top inspection so that it works properly/ down button sticks amd keeps car operating after let go of | 2/26/2021 |
| conversion | conversion | n/a | No | No | Emergency lighting and alarm not working | 2/26/2021 |
| conversion | conversion | n/a | No | No | Repair alarm bell | 2/26/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Install guard on light top of car | 2/26/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Post current State certificate in machine room | 2/26/2021 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | Repair stop switch car | 6/24/2019 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)3 | No | No | Install guard on light on top of car | 2/26/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 2/26/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 2/26/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service testing & document on log in machine room | 2/26/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Repair stop switch in car | 2/26/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Need Mcp on site indicating testing procedures located in machine room | 10/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency light and alarm bell shall be operational. | 5/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Top of car needs to be cleaned. | 12/15/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/15/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Provide monthly fire service testing/log. | 12/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | A working car top light shall be provided. | 12/15/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Remove all non-elevator related materials from the machine room. | 12/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 12/15/2023 |