Inspection
Inspection Details
Equipment ID
20125
20125
Inspection Date
10/28/2025
10/28/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Mark Brown
Mark Brown
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
56a97160-6cd4-47f2-86c1-ec3702de77fe
56a97160-6cd4-47f2-86c1-ec3702de77fe
Location
West County Center
80 W COUNTY CTR, DES PERES, MO
Phone: (314) 984-0450
80 W COUNTY CTR, DES PERES, MO
Phone: (314) 984-0450
Owner
Attn: Andrew Goldacker
CBL Properties/West County Center
80 W County Center, Des Peres, MO 63131
Phone: (314) 288-2026
Alt Phone: (314) 409-8204
Email: andrew.goldacker@cblproperties.com
CBL Properties/West County Center
80 W County Center, Des Peres, MO 63131
Phone: (314) 288-2026
Alt Phone: (314) 409-8204
Email: andrew.goldacker@cblproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.4 - Entrance and egress ends | 6.1.3.12 | No | No | Multi section landing plates are warped (top and bottom) and not level, causing a tripping hazard. Repair | 10/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.4 - Entrance and egress ends | 6.1.3.12 | No | No | Walking surface adjacent to top landing plate is not level with landing plate causing a tripping hazard. Repair | 10/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.3 - Controller and wiring | 6.1.7 | Yes | No | Controller inspection operation does not work. | 10/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.7 - Combplate and comb step impact device | 6.1.8.3 | Yes | No | Comb plate impact device is not moving freely. Test for tripping pressure. | 10/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.9 - Steps and upthrust device | 6.1.3.5 | Yes | No | Replace broken demarcation strip. | 10/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.4 - Entrance and egress ends | 8.6.8.13 | No | No | Repair trip hazard on top floor plate. | 10/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.12 - Steps, step chains, and trusses | 8.11.4.2.12 | No | No | Step chains are worn. Steps are 1/4" out of square with comb plates. Replace step chains. | 9/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.5 - Lighting | 6.1.6.7 | No | No | Replace broken step demarcation strips. | 11/3/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.13 - Handrail systems and safety devices | 8.11.4.2.13 | No | No | Right side handrail drive belt missing. | 11/3/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.11 - Skirt obstruction device | 6.1.6.3.6 | Yes | No | Bottom skirt switches do not work. | 9/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 8.6.8.15 | No | No | Clean truss space and pits. | 11/3/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 8.6.8.13 | No | No | Clean trusses and pit. | 8/16/2021 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.14 Escalator Entrance and Egress Ends | No | No | Bottom walk plate loose, tripping hazard. Re-inspection required | 12/7/2022 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Need to clean truss & pits | 12/7/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.3 - Handrails | 8.6.8.1 | No | No | Right side handrail is dry rotting and cracking in multiple places creating pinching hazards. Replace hand rail | 11/4/2025 |