Inspection
Inspection Details
Equipment ID
23058
23058
Inspection Date
11/29/2017
11/29/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
21/22
21/22
External ID
Location
SSM St. Joseph Med-
100 Medical Plaza, Lake St. Louis, MO
Phone: (636) 625-5319
100 Medical Plaza, Lake St. Louis, MO
Phone: (636) 625-5319
Owner
SSM St. Joseph Hospital-West
100 Medical Plaza, Lake St. Louis, MO 63367
100 Medical Plaza, Lake St. Louis, MO 63367
Billing
Attn: SSM St. Joseph Healthcare
100 Medical Plaza, , MO 63367
100 Medical Plaza, , MO 63367
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair this phone for proper operation and passenger safety. Reinspection required. | 1/20/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The signage for “In Case of Fire Use Stairs” is not located on all landings.. Install signage that conforms to the building code this elevator was installed to meet. | 3/1/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 1/29/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 1/20/2026 |
| A17.1-2016 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | Yes | No | Hoistway access switch not operating at the top and bottom floor. Re-inspection required | 1/20/2026 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.10.2.2.1(r) | Yes | No | Door restriction missing flag / bracket on rear door. Re-inspection required | 1/20/2026 |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 2.13.4.2.3 | Yes | No | Door closing force is greater than 30 lbs. Re-inspection required | 1/20/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.17.15 | Yes | No | Governor remote trip/reset inoperable. Will not set the governor from machine room for testing, repair or replace. Re-inspection required | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete. Cellinoid that sets the overhead governor from machine space does not set the governor. Cellinoid needs to be repaired or replaced and full load safety test needs to be performed. Re-inspection required |