Inspection
Inspection Details
Equipment ID
27177
27177
Inspection Date
10/24/2025
10/24/2025
Inspection Type
New Installation
New Installation
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Ryan Sheahan
Ryan Sheahan
Relief Valve Pressure
530
530
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
24/22
24/22
External ID
b85fdff9-6b28-4e13-937c-80be848fee13
b85fdff9-6b28-4e13-937c-80be848fee13
Location
Huntline Dental
1865 Highway 63, Westphalia, MO
Phone: (573) 455-2710
Email: klbock81@outlook.com
1865 Highway 63, Westphalia, MO
Phone: (573) 455-2710
Email: klbock81@outlook.com
Owner
Attn: Korie Bock
Huntline Dental
1865 Highway 63, Westphalia, MO 65085
Phone: (573) 455-2710
Email: klbock81@outlook.com
Huntline Dental
1865 Highway 63, Westphalia, MO 65085
Phone: (573) 455-2710
Email: klbock81@outlook.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication does not work, line is dead. | 11/18/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | Yes | No | Standby power/Emergency generator system/Add-a-phase system faults with full load capacity test is attempted. | 11/18/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | Yes | No | Standby power system does not send pre-warn signal before swapping back to utility power. | 11/18/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.4.8 Machine Room and Machinery Space | Yes | No | Machine room lighting is less than 19ftc at floor level. | 11/18/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.4.8 Machine Room and Machinery Space | Yes | No | Wall penetrations & gaps to be properly fire-caulked | 11/18/2025 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.10.2.2.2(r) | Yes | No | Phase converter shall have a disconnecting means that is readily accessible and located in sight of the phase converter in the machine room | 11/18/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 8.7.2.1.1 Hoistway Enclosure Walls | Yes | No | Wall penetrations & gaps to be properly fire-caulked. | 11/18/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | Yes | No | There is a drain pipe dumping into sump. Cannot introduce liquids into pit/hoistway | 11/18/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.10.2.2.5(a) | Yes | No | GFI and sump outlets are less than 48" off pit floor, therefore shall have water-resistanct boxes and covers. | 11/18/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.10.2.2.5(a) | Yes | No | 4X4 electrical box has a hole that exposes wire. | 11/18/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.10.2.2.5(a) | Yes | No | Pit ladder rungs shall have at least 4" clearance to wall with out obstruction. (conduit infringes top foot rung) | 10/30/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.10.2.2.5(a) | Yes | No | Wall penetrations & gaps to be properly fire-caulked. | 10/30/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | Yes | No | Sump discharge piping shall be fire-resistant. | 10/30/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.10.2.2.5(a) | Yes | No | Lighting is less than 10ftc at the front of pit (measured 8ftc) | 10/30/2025 |