Inspection
Inspection Details
Equipment ID
5879
5879
Inspection Date
11/7/2025
11/7/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Joseph Ammons
Joseph Ammons
Relief Valve Pressure
n/a
n/a
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
n/a
n/a
External ID
e8b7b2fd-6e2b-4a67-966a-fd3d5e2e272a
e8b7b2fd-6e2b-4a67-966a-fd3d5e2e272a
Location
Dulle Tower
10 Jackson St, Jefferson City, MO
Phone: (573) 635-6163
10 Jackson St, Jefferson City, MO
Phone: (573) 635-6163
Owner
Attn: Jefferson City Housing Authority
Jefferson City Housing Authority
PO Box 1029, Jefferson City, MO 65102
Phone: (573) 635-6163
Jefferson City Housing Authority
PO Box 1029, Jefferson City, MO 65102
Phone: (573) 635-6163
Billing
Attn: Jefferson City Housing Authority
Jefferson City Housing Authority
PO Box 1029, Jefferson City, MO 65102
Phone: (573) 635-6163 Ext: 203
Jefferson City Housing Authority
PO Box 1029, Jefferson City, MO 65102
Phone: (573) 635-6163 Ext: 203
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.3 | Yes | No | Machine room upper handrail is loose. Repair or replace. | 9/15/2023 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | Machine room shall have GFCI outlet. It is currently a standard outlet. | 9/15/2023 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | 4x4 electrical box in machine room needs to have wiring inside box and cover installed. | 9/15/2023 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Low voltage wiring draped across machine room ceiling. Shall be properly encased and plumbed. | 9/15/2023 |
| A17.1-2016 : Elevators | 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches | 3.29 | Yes | No | Machinery, controllers, governors & disconnects shall be numbered conspicuously. | 9/15/2023 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | NEC 110.26 - Disconnects do not meet 30" rule i.e. not co-planer. | 9/15/2023 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 2.24.8.3 | Yes | No | 2.24.8 - Machine brake holding adjustment shall be properly sealed to prevent unauthorized adjustment. | 9/15/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Building fire alarm initiating devices/panel not currently wired to elevator controller. Must be tested for proper FAID recall operation prior to public use. | 9/15/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing is incomplete. Elevator shut down during testing. Category 1 & 5 testing items shall be witnessed. | 9/15/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | Testing is incomplete. Unable to complete tests due to shutdown during test. Items remaining: 125% unintended movement down, 100% safety set, slide, fire service 1 & 2, door force. | 9/19/2023 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Low voltage wiring draped across machine room ceiling. Shall be properly encased and plumbed. | 9/19/2023 |
| A17.1-2016 : Elevators | 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches | 3.29 | Yes | No | Machinery, controllers, governors & disconnects shall be numbered conspicuously. | 9/19/2023 |
| A17.1-2016 : Elevators | 2.27 - Rope fastenings | 2.20.9 | Yes | No | Suspension rope tail ends shall be properly seized/banded. | 9/19/2023 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | Cartop wireway and 4x4 box covers to be installed. | 9/19/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Adjust upthrust roller bearings for proper clearance to door hanger track. (Multiple floors) | 9/19/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone breaking up and full of static. Contact can't tell location. | 11/8/2025 |