Inspection
Inspection Details
Equipment ID
12668
12668
Inspection Date
10/27/2025
10/27/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
38cf41ee-e970-42e9-bccd-422893d26964
38cf41ee-e970-42e9-bccd-422893d26964
Location
West County Center
44 W County Ctr, Des Peres, MO
Phone: (314) 288-2020
44 W County Ctr, Des Peres, MO
Phone: (314) 288-2020
Owner
Attn: Andrew Goldacker
CBL Properties/West County Center
80 W County Center, Des Peres, MO 63131
Phone: (314) 288-2026
Alt Phone: (314) 409-8204
Email: andrew.goldacker@cblproperties.com
CBL Properties/West County Center
80 W County Center, Des Peres, MO 63131
Phone: (314) 288-2026
Alt Phone: (314) 409-8204
Email: andrew.goldacker@cblproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace broken step chip | 10/8/2019 |
| conversion | conversion | n/a | No | No | Repair alarm on top stop switch cover | 10/8/2019 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 806.2 | No | No | Upper and lower demarcation lights are not working. Repair | 10/8/2019 |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 1206.6a | No | No | Upper level machine spaces need to be cleaned out. | 10/8/2019 |
| A17.1-1996 : Escalators | 8.2 - Stop switch | 210.2 | No | No | Upper level stop switch buzzer does not work. | 10/8/2019 |
| A17.1-1996 : Escalators | 7.15 - Balustrades | 802.3 | No | No | Upper left clamping strip is broken. Needs to be replaced. | 10/8/2019 |
| A17.1-1996 : Escalators | 7.15 - Balustrades | 802.3 | No | No | Bottom right deck guard is missing and left side is at wrong height. | 10/8/2019 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 801.1 | No | No | Replace broken stop. Step tread is broke off. | 10/8/2019 |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 1206.6a | No | No | Pit needs to be cleaned. | 9/28/2020 |
| A17.1-1996 : Escalators | 7.10 - Operating and safety devices | 805.3a | No | No | Stop switch buzzer on top not working. | 9/28/2020 |
| A17.1-1996 : Escalators | 8.4 - Drive machine and brake | 804 | Yes | Yes | Brake solenoid failed, replace. Re-inspection required | 3/20/2023 |
| A17.1-1996 : Escalators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(3) Escalators Placed out of Service | Yes | Yes | Step indexing & comb plate impact devices need testing, brake solenoid needs replaced | 3/20/2023 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 1008.2m Handrails | No | No | Left handrail has cracks with pinch points and shall be replaced | 11/12/2025 |
| A17.1-1996 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 1008.2s | No | No | Adjust top right skirt for proper clearance | 8/13/2026 |
| A17.1-1996 : Escalators | 7.4 - Entrance and egress ends | 802.12 | No | No | Repair inoperative demarcation lights | 8/13/2026 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 801.1 | No | No | Clean down Truss | 8/13/2026 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 1008.2m Handrails | Yes | No | Left handrail has cracks with pinch points and shall be replaced | 8/13/2026 |