Inspection
Inspection Details
Equipment ID
6780
6780
Inspection Date
11/13/2025
11/13/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Amador
Michael Amador
Mechanic Name
Kaleb Worley
Kaleb Worley
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
24
24
External ID
a833bcf1-1d34-4b45-a52b-68352bbcd8f8
a833bcf1-1d34-4b45-a52b-68352bbcd8f8
Location
Hotel Indigo
501 Olive St, St. Louis, MO
Phone: (314) 361-7117
501 Olive St, St. Louis, MO
Phone: (314) 361-7117
Owner
Attn: LaSalle Building
Olive Street St Louis LLC
509 Olive St, Ste 400, St. Louis, MO 63101
Phone: (000) 000-0000
Olive Street St Louis LLC
509 Olive St, Ste 400, St. Louis, MO 63101
Phone: (000) 000-0000
Billing
Attn: Olive Street St Louis LLC
Olive Street St Louis LLC
1290 W Spring St SE, Smyrna, GA 30080
Phone: (314) 451-3401
Email: KPrainito@midashospitality.com
Olive Street St Louis LLC
1290 W Spring St SE, Smyrna, GA 30080
Phone: (314) 451-3401
Email: KPrainito@midashospitality.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator machine room. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | The GFI in the controller shall be operational. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency power operation of the elevators shall be tested as part of the annual inspection. | 4/30/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 | Yes | No | Provide code compliant counterweight runby. | 4/30/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.11.2.1.3(w) | No | No | The missing door hall door guide at the 11th floor shall be replaced. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The means to restrict opening of the car door shall be operational. | 2/4/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The two-way communication means shall provide on demand to authorized personnel, information that identifies the building location and elevator number and that assistance is required. Note: The company monitoring the phone was not able to provide location information. | 9/21/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. – 8.6.1.4 or 8.6.10.1 | 9/23/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/23/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.29 - Car and counterweight safeties | 8.11.2.2.2 | Yes | Yes | PERFORM 5-Year full load CAT 5 test. Re-Inspect within 30 days | 5/2/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.3.5 | Yes | No | Test emergency generator | 5/2/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) | 8.6.11.1 | No | No | Perform monthly fire service test and document on the log posted in the machine room. | 3/12/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) | 8.6.11.1 | No | No | PERFORM MONTHLY FIRE SERVICE TEST AND DOCUMENT ON THE LOG POSTED IN THE MACHINE ROOM | 3/12/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 | Yes | No | Repair shunt trip module for proper operation. | 6/13/2025 |