Inspection
Inspection Details
Equipment ID
7991
7991
Inspection Date
10/20/2025
10/20/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Scott Bishop
Scott Bishop
Relief Valve Pressure
NA
NA
Slide
14
14
Governor Rope Pull
63/630
63/630
Door Closing Force
24
24
External ID
908470be-a288-4e13-b1e5-f0424fca30c0
908470be-a288-4e13-b1e5-f0424fca30c0
Location
MO Baptist Medical Center- Bldg D
3023 N Ballas Rd, St. Louis, MO
Phone: (314) 922-9339
Email: bjcinvoices@cushwake.com
3023 N Ballas Rd, St. Louis, MO
Phone: (314) 922-9339
Email: bjcinvoices@cushwake.com
Owner
Attn: BJC C/O Cushman Wakefield
BJC C/O Cushman Wakefield
8300 Eager Rd, St. Louis, MO 63144
Phone: (000) 000-0000
Email: bjcinvoices@cushwake.com
BJC C/O Cushman Wakefield
8300 Eager Rd, St. Louis, MO 63144
Phone: (000) 000-0000
Email: bjcinvoices@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Complete annual insption-test fire service | 5/28/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Car would not operate on emergency power. Emergency operation of the elevator shall function and be tested. | 10/14/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit of dirt and debris. | 12/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 12/28/2022 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Ropes are undersized and have excessive rouging. | 3/1/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power operation of the elevator shall be tested. All units in Building D are due for this testing. | 3/1/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Ropes are undersized and have excessive rouging. (Violation still not corrected/re-inspected as on 3/1/24) | 7/3/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Ropes are undersized and have excessive rouging. This violation has been cited 2 times prior and has not been fixed. Third and final reinspection within 15 days (7/18/24), if not compliant, unit must be red-tagged and removed from service. | 7/31/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. Dials, answered, operator can hear us, but we cannot understand her (intermittent speaker). | 7/31/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean. Remove excess debris. | 11/14/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | The suspension ropes shall be tagged as specified by CSR 40-5.065(L)1. A tag was not provided for the new ropes. | 11/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pits shall not be used for storage purposes. There are two large extension ladders being stored in the pit. | 11/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. Dials, answered, operator can hear us, but we cannot understand her (intermittent speaker). Violation not cleared as of 7/31/2024. | 11/14/2025 |