Inspection
Inspection Details
Equipment ID
12597
12597
Inspection Date
10/31/2025
10/31/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Amador
Michael Amador
Mechanic Name
Timothy Neulist
Timothy Neulist
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
a0d47a0a-d41d-4314-86af-aec899d9a1f2
a0d47a0a-d41d-4314-86af-aec899d9a1f2
Location
Peabody Plaza
701 Market St, Ste 1230, St. Louis, MO
Phone: (314) 241-1175
701 Market St, Ste 1230, St. Louis, MO
Phone: (314) 241-1175
Owner
Attn: Daniel Hutkins
SPV XVII, LLC
701 Market St, Ste 1200, St. Louis, MO 63101
Phone: (314) 241-1175
Email: Daniel.hutkins@cbre.com
SPV XVII, LLC
701 Market St, Ste 1200, St. Louis, MO 63101
Phone: (314) 241-1175
Email: Daniel.hutkins@cbre.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 11/16/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | 11/16/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | The signage for “In Case of Fire” the missing. Install signage that conforms to the building code this elevator was installed to conform to. | 11/16/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | When testing the ADA telephone with the 110V disconnect in the machine room in the “off” position, the device failed to operate, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 5/16/2024 | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to conform to. | 11/16/2025 | ||
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | x | Machine room door shall be self-closing and self-locking. | 5/28/2024 | |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | x | Disconnect breaker jams, not allowing for proper opening of mainline circuit. | 5/28/2024 | |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | x | Disconnects does not have 36" workspace clearance to nearest object (air handler). | 5/28/2024 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency power must be tested. | 5/28/2024 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency power must be tested. | 11/16/2025 | |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Top of Cars | Car top shall be cleaned. | 2/8/2026 | ||
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Top of Cars | Car top shall be cleaned |