Inspection
Inspection Details
Equipment ID
13334
13334
Inspection Date
10/31/2025
10/31/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Amador
Michael Amador
Mechanic Name
Timothy Neulist
Timothy Neulist
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
24
24
External ID
0d12b511-33e6-4176-8937-e1739d4a4485
0d12b511-33e6-4176-8937-e1739d4a4485
Location
Peabody Plaza
701 Market St, Ste 1230, St. Louis, MO
Phone: (314) 241-1175
701 Market St, Ste 1230, St. Louis, MO
Phone: (314) 241-1175
Owner
Attn: Daniel Hutkins
SPV XVII, LLC
701 Market St, Ste 1200, St. Louis, MO 63101
Phone: (314) 241-1175
Email: Daniel.hutkins@cbre.com
SPV XVII, LLC
701 Market St, Ste 1200, St. Louis, MO 63101
Phone: (314) 241-1175
Email: Daniel.hutkins@cbre.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Hoist ropes need to be shortened. | 1/21/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 11/16/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | 11/16/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | The signage for “In Case of Fire” the missing. Install signage that conforms to the building code this elevator was installed to conform to. | 11/16/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | A guide roller on top of the car has degraded to the point that replacement is required on the elevator car. Replace degraded roller.. | 11/16/2025 | ||
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to conform to. | 11/16/2025 | ||
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Machine room rescue phone is not working. | 1/21/2025 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | Counterweight governor cable is rubbing side of MR floor opening. | 1/21/2025 | |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.4.19.13 Broken Suspension Member and Residual Strength Detection Means | x | Belt switches do not individually trigger. | 1/21/2025 | |
| A17.1-2016 : Elevators | 3.8 - Top emergency exit | 2.14.1.5 | x | Cartop escape hatch latch is missing. | 1/21/2025 | |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | x | Hoistway doors to open fully, currently most stop approximately 2" short of full open. | 1/21/2025 | |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 | x | Adjust all upthrusts for proper door to door gap (center opening, at bottom). | 1/21/2025 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | x | Remove existing pit ladder (unit has a walk-in pit door) or install additional stop switches and relocate for proper clearance to wall (4.5"). | 1/21/2025 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency power, fire status panel, and group FAID to be fully tested at the time of the "Final-Final" (likely to be car 10). | 1/21/2025 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency power, fire status panel, and group FAID to be fully tested at the time of the "Final-Final" (likely to be car 10). | 11/16/2025 |