Inspection
Inspection Details
Equipment ID
20019
20019
Inspection Date
1/21/2019
1/21/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Bobby Joe Mehrens
Bobby Joe Mehrens
Relief Valve Pressure
Na
Na
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
54219bc8-82c5-4698-b250-9c3cbb54a1ed
54219bc8-82c5-4698-b250-9c3cbb54a1ed
Location
Shumaker
500 COLLEGE HL, LIBERTY, MO
500 COLLEGE HL, LIBERTY, MO
Owner
William Jewel College
500 COLLEGE HL, LIBERTY, MO 64068-1843
500 COLLEGE HL, LIBERTY, MO 64068-1843
Billing
Attn: William Jewel College
500 COLLEGE HL # 1110, LIBERTY, MO 64068-1843
500 COLLEGE HL # 1110, LIBERTY, MO 64068-1843
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency light and bell do not operate | 1/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency return unit does not supply auxillary power. | 1/21/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Test and log firefighter operation monthly. | 8/10/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Post emergency evacuation of passengers form inside machine room. | 8/10/2026 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Emergency light does not operate. | 1/27/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate inside machine room. | 8/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.2 | No | No | Number inside of hoistway doors for identification. | 8/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Test and log firefighter operation monthly | 8/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Post emergency evacuation of passengers procedure in the machine room | 8/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.7.2 Periodic Test Record (Test Tags) | No | No | Install metal test tag for periodic pressure relief test | 8/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room | 8/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | No | No | Identify the inside of hoistway doors with a numeral corresponding to the landing floor | 8/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | No | No | Install cylinder drain line hose and pit collection container. | 8/10/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No maintenance control plan | 8/10/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance records on site | 8/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.7.2 Periodic Test Record (Test Tags) | No | No | Attach metal test tag for documentation of periodic annual pressure relief test | 8/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed in machine room | 8/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | Post In Case of Fire signage next to hall button fixture at each landing | 8/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Machine room mainline breaker disconnect is not lockable in the open position | 8/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Machine room 110 volt cab lighting breaker disconnect is not lockable in the open position | 8/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | No | No | Install cylinder drain line and pit collection container | 8/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 8/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Main line disconnect not capable of being locked in the open position. | 8/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | 110VAC car light disconnect not capable of being locked in the open position. | 8/10/2026 |