Inspection
Inspection Details
Equipment ID
20301
20301
Inspection Date
11/3/2025
11/3/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Kevin Hecht
Kevin Hecht
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
a491f3be-97ff-40cf-92a5-f00ad1a2ba61
a491f3be-97ff-40cf-92a5-f00ad1a2ba61
Location
Hampton Inn & Suites
4200 Mid America Ln, St. Louis, MO
Phone: (314) 894-1900
4200 Mid America Ln, St. Louis, MO
Phone: (314) 894-1900
Owner
Attn: Renee Williams
Midamerica Hotels Corp
105 S Mt Auburn Rd, Cape Girardeau, MO 63702
Phone: (573) 334-0546
Alt Phone: (573) 388-2436
Email: rwilliams@midamcorp.com
Midamerica Hotels Corp
105 S Mt Auburn Rd, Cape Girardeau, MO 63702
Phone: (573) 334-0546
Alt Phone: (573) 388-2436
Email: rwilliams@midamcorp.com
Billing
Attn: Renee Williams
Midamerica Hotels Corp
4072 State Highway K, Cape Girardeau, MO 63701
Phone: (573) 334-0546
Alt Phone: (573) 388-2436
Email: rwilliams@midamcorp.com
Midamerica Hotels Corp
4072 State Highway K, Cape Girardeau, MO 63701
Phone: (573) 334-0546
Alt Phone: (573) 388-2436
Email: rwilliams@midamcorp.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell does not work. | 12/17/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide written maintenance control program on site for each elevator. | 11/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell in elevator does not work, Re-inspect in 30 days | 5/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | The emergency power indicating jewel failed to operate when activated, repair light jewel to activate as required. | 11/21/2025 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.3.2 (Re-Inspection) | Yes | No | The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Replace ropes within 30 days of inspection. Reinspection is required. | 11/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power needs to be tested. | 2/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not give location and the recording says that it is not an emergency and is a test call. | 2/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 2.14.1.7 Railing and Equipment on Top of Cars | Yes | No | The cartop handrails are loose and shall be tightened. | 2/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power needs to be tested. | 11/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 2.14.1.7 Railing and Equipment on Top of Cars | Yes | No | The cartop handrails are loose and shall be tightened. | 11/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power needs to be tested. | 12/2/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.17.15 | Yes | No | Governor reset solenoid is not functioning and needs repaired/replaced. | 4/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two-way communication device is not functioning and needs repaired. | 4/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.1 | Yes | No | Counterweight runby is greater than minimun distance allowed, blocking must be installed to achieve proper runby of 6" | 4/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | Yes | No | Emergency power jewel must be checked when emergency power is tested. | 4/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.16.8 | Yes | No | Emergency power operation must be tested. | 4/6/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Break test, setting of safties, unintended motion, and ascending overspeed must be completed to satisfy full cat 5 test. These things could not be done due to repair needed on the governor reset solenoid. | 4/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.16.8 | Yes | No | Emregency power and emergency power jewel operations could not be tested due to faliure of generator operation. | 8/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.5 | Yes | No | Suspension-rope equalizers, shall be of the individual compression spring type. two(2) equalizer springs on machine side hitch are broken. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.5 | Yes | No | Shackle rod threading shall have a cotter pin or equivalent to prevent unscrewing of the connection in normal operation. One(1) cotter pin is broken on machine side hitch. |