Inspection
Inspection Details
Equipment ID
11152
11152
Inspection Date
11/6/2025
11/6/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
NA
NA
Slide
30"
30"
Governor Rope Pull
45/800
45/800
Door Closing Force
15
15
External ID
6bf4ac1e-5ba6-4ae7-af9a-fbf28f59aaca
6bf4ac1e-5ba6-4ae7-af9a-fbf28f59aaca
Location
Station Plaza Limited Partnership
1900 Pine St, St. Louis, MO
Phone: (314) 657-7720
Email: Timothy.Wonsewitz@BCBSMO.COM
1900 Pine St, St. Louis, MO
Phone: (314) 657-7720
Email: Timothy.Wonsewitz@BCBSMO.COM
Owner
Attn: Station Plaza Limited Partnership
Station Plaza Limited Partnership
233 Park Ave, Ste 201, Minneapolis, MN 55415
Phone: (000) 000-0000
Station Plaza Limited Partnership
233 Park Ave, Ste 201, Minneapolis, MN 55415
Phone: (000) 000-0000
Billing
Attn: Jill S. Belsky
Station Plaza Limited Partnership
3630 Grandel Sq, St. Louis, MO 63108
Phone: (314) 454-0800 Ext: 307
Email: jbelsky@rcirealty.com
Station Plaza Limited Partnership
3630 Grandel Sq, St. Louis, MO 63108
Phone: (314) 454-0800 Ext: 307
Email: jbelsky@rcirealty.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)5 | A code compliant ladder shall be installed in the elevator pit. | 12/9/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | A current tested fire extinguisher is required in the elevator machine room. | 12/9/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display a current state operating certificate. | 12/9/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.11.3.1.5 (j) Car Safety | x | A category 5 safety test shall be performed. | 12/9/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide a written MCP. | 12/9/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | The machine room shall not be used for the storage of non-elevator related material. | 12/9/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 8.11.2.1.3(b) | The car top light shall be operational. | 12/9/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | The pit shall be kept clean. | 12/9/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The emergency alarm bell shall be operational. | 12/9/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | Phase 2 fire service shall be operational. (Maintenance company attempted to fix, but unable to. Unit due for MOD in May 2020). | 12/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 8.11.2.1.1(h) | x | The door closing force shall be under 30 lbs. | 12/16/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | x | Provide code compliant pit lighting at all areas of the pit. The pit lighting shall be a minimum of 10 ftc. | 12/16/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | x | Properly fix the hole in the pit wall near piping. | 12/16/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | x | An MCP shall be kept on-site. | 12/16/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | x | The flashing hat feature on fire service shall be operational when the smoke detectors in the hoistway and machine room are activated. | 12/16/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.22 - Wire rope fastening and hitch plate | 8.11.2.1.3(bb) | x | The hoist ropes shall be properly secured in the shackles. | 12/16/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.1 - Car platform guard | 2.15.9 | x | The toe guard shall be 48" long. If pit depth in inadequate to support a 48" toe guard a variance shall be applied for. | 12/16/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 Access to Pit | x | The pit ladder shall be code compliant. If a code compliant pit ladder will not fit in the pit a variance shall be applied for. | 12/16/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | x | The gaps between the hoistway door panels and frames shall not exceed 3/8". If code compliant gaps cannot be achieved, a variance shall be applied for. | 12/16/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 1/26/2022 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall work. | 12/3/2025 |