Inspection
Inspection Details
Equipment ID
17065
17065
Inspection Date
11/13/2025
11/13/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Kurt Warttig
Kurt Warttig
Relief Valve Pressure
NA
NA
Slide
4.5"
4.5"
Governor Rope Pull
40/200
40/200
Door Closing Force
16
16
External ID
cdaf229f-55dc-4c2b-857e-5523aab10b6f
cdaf229f-55dc-4c2b-857e-5523aab10b6f
Location
Cupples Station Apartments
1023 Spruce St, St. Louis, MO
Phone: (314) 241-1225
1023 Spruce St, St. Louis, MO
Phone: (314) 241-1225
Owner
Attn: Cupples Station, LLC
Cupples Station, LLC
1023 Spruce St, St. Louis, MO 63102
Phone: (000) 000-0000
Email: etammas@fwresults.com
Cupples Station, LLC
1023 Spruce St, St. Louis, MO 63102
Phone: (000) 000-0000
Email: etammas@fwresults.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide MCP | 7/7/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Provide testing | 7/7/2022 |
| A17.1-1996 : Elevators | 4.12 - Standby power selection switch | 1002.2g | No | No | Provide testing | 7/17/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Emergency Power was not transferred to the elevator during testing | 7/7/2022 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | Ropes are rusted and undersized, need to replace all hoist ropes. Re-inspection required | 7/12/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 7/11/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/9/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-WAY COMMUNICATION DEVICE SHALL WORK. No Answer | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually. | |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | No | No | Investigate and repair the source of the grinding noise at the hoist machine. | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. There are no schematics, on-site(as well as fault code lists and parameter tables) | |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 201 | No | No | Need to change worn/damaged upper car roller guides and lower counterweight roller guides. | |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 210.13 | No | No | Replace missing/damaged/faded "Do not use elevator in case of fire" Signage on multiple floors. | |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 210.13 | No | No | Replace damaged Phase 2 instructions inside car. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean. Remove excess debris |