Inspection
Inspection Details
Equipment ID
8475
8475
Inspection Date
11/13/2025
11/13/2025
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Benjamin Postawko
Benjamin Postawko
Relief Valve Pressure
NA
NA
Slide
TBD
TBD
Governor Rope Pull
350/880
350/880
Door Closing Force
TBD
TBD
External ID
0e1c3502-979c-4541-b63a-4808f7faf366
0e1c3502-979c-4541-b63a-4808f7faf366
Location
Boeing Bldg #100
McDonnell Blvd & Airport Rd, Berkeley, MO
Phone: (314) 234-6485
Email: shelbi.paulson@boeing.com
McDonnell Blvd & Airport Rd, Berkeley, MO
Phone: (314) 234-6485
Email: shelbi.paulson@boeing.com
Owner
Attn: Ronald Johnson
Boeing Co
PO Box 516, St. Louis, MO 63166
Phone: (314) 409-2954
Email: Ronald.Johnsoniii@JLL.com
Boeing Co
PO Box 516, St. Louis, MO 63166
Phone: (314) 409-2954
Email: Ronald.Johnsoniii@JLL.com
Billing
Attn: Boeing Co
Boeing Co
PO Box 516, St. Louis, MO 63166
Phone: (314) 234-6485
Email: stlinvoice@boeing.com
Boeing Co
PO Box 516, St. Louis, MO 63166
Phone: (314) 234-6485
Email: stlinvoice@boeing.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Door closing exceeds 30 pounds needs adjsuting | 6/14/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car not working | 6/14/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair emergency light | 11/21/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 11/21/2025 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.3.2 (Re-Inspection) | Yes | No | Ropes appear to be rubbing top of hoistway spinkler pipe. Check and take corrective action. | 1/27/2026 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | Yes | No | Adjust 2nd floor hoistway door upthrust rollers for proper clearance. (lower gap>1") | 1/27/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | FAID recall not working properly | 1/27/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need all CAT5 test items performed except POPY nad Gov spin, Fire service 1&2, finals, ETS, NTS, and items found on 17.2 list. | 1/27/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | Yes | No | Test emergency power. | 1/27/2026 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | Yes | No | Upper machine level guardrail is only 32" in height. shall be standard height (42") with midrail (21") and toe kick in the machine room. | 1/27/2026 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | Upper machine level lighting shall not be less than 19ftc in the machine room. | 1/27/2026 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.10.2.2.2(r) | Yes | No | Disconnects shall be labeled with location feeder breakers and function in the machine room. | 1/27/2026 |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.5 | Yes | No | All ledges greater than 4"shall be properly gaurded and/or beveled at 70deg. | 1/27/2026 |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.6 | Yes | No | Walkway at top of hoistway shall have proper standard handrail w/toekick or 70deg bevel installed. | 1/27/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | Yes | No | Test emergency power. | |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | Yes | No | Upper machine level guardrail is only 32" in height. shall be standard height (42") with midrail (21") and toe kick in the machine room. | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | Upper machine level lighting shall not be less than 19ftc in the machine room. | |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.10.2.2.2(r) | Yes | No | Disconnects shall be labeled with location feeder breakers and function in the machine room. | |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.5 | Yes | No | All ledges greater than 4"shall be properly gaurded and/or beveled at 70deg. | |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.6 | Yes | No | Walkway at top of hoistway shall have proper standard handrail w/toekick or 70deg bevel installed. |