Inspection
Inspection Details
Equipment ID
10356
10356
Inspection Date
10/31/2025
10/31/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Chad Hackstadt
Chad Hackstadt
Mechanic Name
Jeffrey Woods
Jeffrey Woods
Relief Valve Pressure
NA
NA
Slide
Softset
Softset
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
e19bd19c-162f-45e7-ac9b-8577e3b67642
e19bd19c-162f-45e7-ac9b-8577e3b67642
Location
Charter Communications
12409 POWERSCOURT DR, SAINT LOUIS, MO
Phone: (314) 727-6664
12409 POWERSCOURT DR, SAINT LOUIS, MO
Phone: (314) 727-6664
Owner
Attn: Charter Communication Holding Co. LLC.
Charter Communication Holding Co. LLC.
12405 Powerscourt Dr, St. Louis, MO 63131
Phone: (000) 000-0000
Charter Communication Holding Co. LLC.
12405 Powerscourt Dr, St. Louis, MO 63131
Phone: (000) 000-0000
Billing
Attn: Sansone Group
Sansone Group
120 S Central Ave, Ste 500, St. Louis, MO 63105
Phone: (000) 000-0000
Email: JBerra@sansonegroup.com
Sansone Group
120 S Central Ave, Ste 500, St. Louis, MO 63105
Phone: (000) 000-0000
Email: JBerra@sansonegroup.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 12/9/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 1/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The means to restrict opening of the car door shall be operational. | 1/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The means to restrict opening of the car door are not operational between floors 1 & 2 and Basement & 1. | 3/9/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The emergency/standby power shall be tested. | 10/15/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service operation shall be tested as required. | 10/15/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall give proper location message. No location message is being given. | 10/21/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 10/21/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service operation shall be tested. | 10/21/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be properly documented monthly on log sheet. The logs are blank. | 1/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Compliant/required documentation shall be kept in equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, and evacuation procedures. | 1/26/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Non-elevator related items (HVAC fans, etc..) shall not be stored in the machine room. | 1/26/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Need all weight tests: 125% down run, 100% set safeties, 100% car buffer, empty car counterweight buffer test, slide. | 10/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall give proper location message. No location message is being given. | 10/24/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Need all weight tests: 125% down run, 100% set safeties, 100% car buffer, empty car counterweight buffer test, slide. | 10/24/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 11/25/2024 |