Inspection
Inspection Details
Equipment ID
11114
11114
Inspection Date
1/22/2019
1/22/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Healy
David Healy
Mechanic Name
Bradley Dreyer
Bradley Dreyer
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
69e7e60d-b3cc-4f54-9748-486572d020ab
69e7e60d-b3cc-4f54-9748-486572d020ab
Location
Central Bank Of The Midwest
11206 E 24TH ST S, INDEPENDENCE, MO
11206 E 24TH ST S, INDEPENDENCE, MO
Owner
Attn: Central Bank of Midwest
Central Bank of Midwest
609 NORTH M 291 HWY, LEES SUMMIT, MO 64086
Phone: (816) 714-6121
Email: Vicky.zurliene@centralbank.ne
Central Bank of Midwest
609 NORTH M 291 HWY, LEES SUMMIT, MO 64086
Phone: (816) 714-6121
Email: Vicky.zurliene@centralbank.ne
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | car lights failed | 7/29/2020 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | No | No | emergency phone failed | 1/8/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Overhead lighting in car not working. | 7/29/2020 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency phone not working. | 1/7/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light not working. | 7/29/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Overhead lighting in machine room not working. | 7/29/2020 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency bell, and lighting weak, and unable to sustain load for test. | 1/7/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 3/11/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone working, but not identifying the location through the carrier's system. | 1/18/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | F.F.S phase I failed to recall after activating key switch | 1/9/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | mach room door lock is defeatable replace with undefeatable door lock | 3/11/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | 3/11/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | Yes | phase one fire serv didnt work elev. didnt respond to key sw or operate on phase one | 3/7/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | mach room door lock is defeatable needs to be undefeatable | 3/11/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency light and bell |