Inspection
Inspection Details
Equipment ID
20053
20053
Inspection Date
11/25/2025
11/25/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Smith
Dennis Smith
Mechanic Name
Justin Kennedy
Justin Kennedy
Relief Valve Pressure
440
440
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
10-F / 14-R
10-F / 14-R
External ID
2bb60815-0ae5-4dcf-a717-3f201ef54d3d
2bb60815-0ae5-4dcf-a717-3f201ef54d3d
Location
MO Western Remington Hall
4525 Downs Dr, St. Joseph, MO
Phone: (816) 383-7143
4525 Downs Dr, St. Joseph, MO
Phone: (816) 383-7143
Owner
Attn: MO Western State University
MO Western State University
4525 Downs Dr, St. Joseph, MO 64507
Phone: (816) 271-4417
Email: phyplant@missouriwestern.edu
MO Western State University
4525 Downs Dr, St. Joseph, MO 64507
Phone: (816) 271-4417
Email: phyplant@missouriwestern.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | Emergency light does not operate | 7/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 3/29/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside machine room | 5/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | No | No | Cylinder drain line needs to be ran to pit collection container of no more than 5 gallon capacity | 5/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency power lowering unit does not supply emergency power to the elevator | 11/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate inside the machine room | 4/7/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | Post In Case of Fire signage next to corridor call station at each landing | 4/7/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Test and log firefighter operation monthly | 4/7/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.2 | No | No | Identify the inside of hoistway doors with a numeral | 4/7/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys (Re-Inspection) | Yes | No | Hall and car firefighter keyswitches shall be operable by the FEO-K1 key. Existing elevator in the same building uses the FEO-K1 keyswitch | 11/22/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone does not operate | 11/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 Gland Packings and Seals | No | No | JACK NEED REPACKING DUE TO EXCESSIVE LEAKAGE | 11/25/2025 |