Inspection
Inspection Details
Equipment ID
6615
6615
Inspection Date
11/26/2025
11/26/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Relief Valve Pressure
480
480
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
23 / 25
23 / 25
External ID
e9a6e043-06cd-4410-9f34-2a68e3d6f4ad
e9a6e043-06cd-4410-9f34-2a68e3d6f4ad
Location
Claymont Place
500 North and South Rd, University City, MO
Phone: (636) 227-8688
500 North and South Rd, University City, MO
Phone: (636) 227-8688
Owner
Attn: Tiffany Rehg
Claymont Place Condo Association c/o Sentry Management
9666 Olive Blvd, Ste 116, St. Louis, MO 63132
Phone: (314) 994-7440 Ext: 57509
Email: trehg@sentrymgt.com
Claymont Place Condo Association c/o Sentry Management
9666 Olive Blvd, Ste 116, St. Louis, MO 63132
Phone: (314) 994-7440 Ext: 57509
Email: trehg@sentrymgt.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 12/6/2018 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Replace broken light fixture in elevator cab. | 10/23/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate in machine room. | 12/29/2020 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Light bulbs in cab need to be guarded to prevent injury to persons in the event of breakage. Open type "egg crate" panels should be replaced with solid panels or plastic tubes to cover bulbs. | 12/29/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed, perform required test & seal on or before next anniversary date | 12/2/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not operable | 10/7/2022 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)6 | No | No | Replace cartop guide shoes to reduce post to post movement of elevator | 12/2/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self closing/locking. Lock cannot be disabled at any time | 12/2/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Replace lighting to insure at least 10 foot candles of illumination at floor level anywhere in machine room. Lights must be guarded against breakage | 12/2/2025 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV has not yet been tested after being wrote up last year. Elevator must have a category 5 weight test performed within 90 days. | 7/13/2023 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)6 | Yes | No | REPLACE CARTOP GUIDE SHOES TO REDUCE POST TO POST MOVEMENT OF ELEVATOR | 7/13/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | MACHINE ROOM DOOR MUST BE SELF CLOSING / SELF LOCKING. LOCK CAN NOT BE ABLE TO BE DISABLED AT ANY TIME. | 7/13/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Yes | No | REPLACE LIGHTING TO INSURE AT LEAST 10 FOOT-CANDLES OF ILLUMINATION AT FLOOR LEVEL ANYWHERE IN MACHINE ROOM. LIGHTS MUST BE GUARDED AGAINST BREAKAGE | 7/13/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate on emergency 110v power or normal power. Repair or replace | 7/13/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Need to replace lighting to insure at least 10 foot candles of illumination at floor level anywhere in machine room. Lights must be guarded against breakage. | 12/2/2025 |