Inspection
Inspection Details
Equipment ID
2045
2045
Inspection Date
1/25/2019
1/25/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Christopher Hughes
Christopher Hughes
Relief Valve Pressure
300
300
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
c6491b18-5249-4747-8ea0-d9b32d4e84fb
c6491b18-5249-4747-8ea0-d9b32d4e84fb
Location
Lee's Summit High School
400 SE BLUE PKWY, LEES SUMMIT, MO
400 SE BLUE PKWY, LEES SUMMIT, MO
Owner
Lee's Summit R-7 School District
502 TRANSPORT DR, LEES SUMMIT, MO 64081-3290
502 TRANSPORT DR, LEES SUMMIT, MO 64081-3290
Billing
Attn: Lee's Summit R-7 School District
502 TRANSPORT DR, LEES SUMMIT, MO 64081-3290
502 TRANSPORT DR, LEES SUMMIT, MO 64081-3290
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency phone dropping call after connection. | 1/19/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Fire service works, but won't reset with the key after testing. | 1/19/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | Pit switch working, but incorrectly labeled. | 3/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Fire service testing log not up to date. | 3/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)2 Alterations | No | No | Fire sprinkler added in machine room during remodeling work. Remove, or provide a shunt trip device and heat detector in machine room. | 3/26/2026 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.3 | Yes | No | Sprinkler line for shunt trip not finished. | 1/18/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. Line? | 4/1/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Shunt trip not overriding battery lowering. Needs relay added | 4/1/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Top of hoistway smoke sensor recalls elevator to wrong floor. Relay needed | 4/1/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Machine room needs 110v receptical | 3/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. Bldg line. | 2/20/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Machine room needs 110v gfci outlet | 3/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. | 8/27/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. | 3/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Jack packing leaking, causing pit jug to overflow. | 3/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. |