Inspection
Inspection Details
Equipment ID
20301
20301
Inspection Date
11/4/2025
11/4/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Kevin Hecht
Kevin Hecht
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
70/210
70/210
Door Closing Force
24
24
External ID
34ca9237-0660-4dba-8506-53655fbe31d1
34ca9237-0660-4dba-8506-53655fbe31d1
Location
Hampton Inn & Suites
4200 Mid America Ln, St. Louis, MO
Phone: (314) 894-1900
4200 Mid America Ln, St. Louis, MO
Phone: (314) 894-1900
Owner
Attn: Renee Williams
Midamerica Hotels Corp
105 S Mt Auburn Rd, Cape Girardeau, MO 63702
Phone: (573) 334-0546
Alt Phone: (573) 388-2436
Email: rwilliams@midamcorp.com
Midamerica Hotels Corp
105 S Mt Auburn Rd, Cape Girardeau, MO 63702
Phone: (573) 334-0546
Alt Phone: (573) 388-2436
Email: rwilliams@midamcorp.com
Billing
Attn: Renee Williams
Midamerica Hotels Corp
4072 State Highway K, Cape Girardeau, MO 63701
Phone: (573) 334-0546
Alt Phone: (573) 388-2436
Email: rwilliams@midamcorp.com
Midamerica Hotels Corp
4072 State Highway K, Cape Girardeau, MO 63701
Phone: (573) 334-0546
Alt Phone: (573) 388-2436
Email: rwilliams@midamcorp.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell does not work. | 12/17/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide written maintenance control program on site for each elevator. | 11/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell in elevator does not work, Re-inspect in 30 days | 5/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | The emergency power indicating jewel failed to operate when activated, repair light jewel to activate as required. | 11/21/2025 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.3.2 (Re-Inspection) | Yes | No | The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Replace ropes within 30 days of inspection. Reinspection is required. | 11/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power needs to be tested. | 2/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not give location and the recording says that it is not an emergency and is a test call. | 2/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 2.14.1.7 Railing and Equipment on Top of Cars | Yes | No | The cartop handrails are loose and shall be tightened. | 2/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power needs to be tested. | 11/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 2.14.1.7 Railing and Equipment on Top of Cars | Yes | No | The cartop handrails are loose and shall be tightened. | 11/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power needs to be tested. | 12/2/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.17.15 | Yes | No | Governor reset solenoid is not functioning and needs repaired/replaced. | 4/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two-way communication device is not functioning and needs repaired. | 4/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.1 | Yes | No | Counterweight runby is greater than minimun distance allowed, blocking must be installed to achieve proper runby of 6" | 4/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | Yes | No | Emergency power jewel must be checked when emergency power is tested. | 4/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.16.8 | Yes | No | Emergency power operation must be tested. | 4/6/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Break test, setting of safties, unintended motion, and ascending overspeed must be completed to satisfy full cat 5 test. These things could not be done due to repair needed on the governor reset solenoid. | 4/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.16.8 | Yes | No | Emregency power and emergency power jewel operations could not be tested due to faliure of generator operation. | 8/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.5 | Yes | No | Suspension-rope equalizers, shall be of the individual compression spring type. two(2) equalizer springs on machine side hitch are broken. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.5 | Yes | No | Shackle rod threading shall have a cotter pin or equivalent to prevent unscrewing of the connection in normal operation. One(1) cotter pin is broken on machine side hitch. |