Inspection
Inspection Details
Equipment ID
27084
27084
Inspection Date
11/14/2025
11/14/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Chad Boxdorfer
Chad Boxdorfer
Relief Valve Pressure
NA
NA
Slide
2.5"
2.5"
Governor Rope Pull
50/190
50/190
Door Closing Force
16
16
External ID
63de5230-24df-4e5f-a7c0-1991cf7049c8
63de5230-24df-4e5f-a7c0-1991cf7049c8
Location
Saint Louis University Hospital Legacy Connector
120 S Central Ave, St. Louis, MO
Phone: (000) 000-0000
Email: tyler.mcclain@alberici.com
120 S Central Ave, St. Louis, MO
Phone: (000) 000-0000
Email: tyler.mcclain@alberici.com
Owner
Attn: SSM Healthcare St Louis
SSM Healthcare St Louis
1015 Corporate square Dr Suite 101, St. Louis, MO 63132
Phone: (000) 000-0000
Email: tyler.mcclain@alberici.com
SSM Healthcare St Louis
1015 Corporate square Dr Suite 101, St. Louis, MO 63132
Phone: (000) 000-0000
Email: tyler.mcclain@alberici.com
Billing
Attn: SLU
SLU
120 S CENTRAL AVE, St. Louis, MO 63105
Phone: (000) 000-0000
Email: tyler.mcclain@alberici.com
SLU
120 S CENTRAL AVE, St. Louis, MO 63105
Phone: (000) 000-0000
Email: tyler.mcclain@alberici.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.19.15 Emergency Communications | x | Communication loss buzzer reset keyswitch does not work | 12/2/2025 | |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.10.2.2.1(h) | x | Door closing force shall be tested. | 12/2/2025 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | x | Emergency power operation shall be tested. | 12/2/2025 | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.4.8 Machine Room and Machinery Space | x | Fire caulk smoke/fire penetrations. | 12/2/2025 | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.10.2.2.2(l) | x | Fire extinguisher shall be permanently mounted adjacent to the door. | 12/2/2025 | |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.10.2.2.2(r) | x | Lighting disconnect is obstructed by main disconnects. (see also NEC/NFPA 110.26) | 12/2/2025 | |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.10.2.3.2(s) | x | Mainline and lighting disconnects to be labeled for function. | 12/2/2025 | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | x | Compliant MCP (with all documentation including evac procedures, wiring diagrams, ect.) needed. | 12/2/2025 | |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.10.2.2.3(w) | x | Adjust upthrust roller bearings for proper clearance to door hanger track on 2nd floor. | 12/2/2025 | |
| A17.1-2016 : Elevators | 3.28 - Counterweight and counterweight buffer | 8.10.2.2.3(m) | x | Counterwights runby (C-measurement) exceeds OEM allowed clearance (currently 9.625" Max = 6.5) | 12/2/2025 | |
| A17.1-2016 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | x | Hoistway acess swtiches (top and bottom) shall not be more than 12" from the entrance frames. Currently mounted on hall call station, approximately 42" from entrance frame. | 11/14/2025 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.3 | x | Pit lighting shall not be less than10fc at the floor level. (Currently 4fc) | 11/14/2025 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | x | Fire service phase I and phase II shall be tested. | 11/14/2025 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | x | All FAID shall be tested for functionality and reacall (heats, shunts, smokes). Smoke detector installation incomplete but observed 2nd floor smoke is less than 36" from HVAC vent. | 11/14/2025 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | x | Emergency power shall be tested. |