Inspection
Inspection Details
Equipment ID
17469
17469
Inspection Date
11/20/2025
11/20/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Relief Valve Pressure
500
500
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
24
24
External ID
4cd18d78-5d2b-45e4-b500-c31853ef93b9
4cd18d78-5d2b-45e4-b500-c31853ef93b9
Location
Cedar Plaza
5000 Cedar Plaza Pkwy, St. Louis, MO
Phone: (314) 843-4333
5000 Cedar Plaza Pkwy, St. Louis, MO
Phone: (314) 843-4333
Owner
Attn: Cedar Plaza
Cedar Plaza
5000 Cedar Plaza Pkwy, St. Louis, MO 63128
Phone: (000) 000-0000
Email: mzahir@charter.net
Cedar Plaza
5000 Cedar Plaza Pkwy, St. Louis, MO 63128
Phone: (000) 000-0000
Email: mzahir@charter.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Light Ray is not overridden on Phase I. | 7/14/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Light ray shall be overridden on Phase 1 fire service. | 2/26/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Provide existing door detection system to be overridden upon activation of Phase 1 fire recall. Deputy Chief Gus Guadamuz has allowed 10 days of operation from 3/30/2020 for the fire service violations to be corrected. The elevator will be red tagged and locked out of service if violations are not corrected. | 6/11/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The emergency lighting shall have 2 working lamps. | 6/11/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Provide existing audible indicator to work upon activation of Phase 1 fire recall. Deputy Chief Gus Guadamuz has allowed 10 days of operation from 3/30/2020 for the fire service violations to be corrected. The elevator will be red tagged and locked out of service if violations are not corrected. | 6/11/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Provide existing visual indicator to work upon activation of Phase 1 recall. Deputy Chief Gus Guadamuz has allowed 10 days of operation from 3/30/2020 for the fire service violations to be corrected. The elevator will be red tagged and locked out of service if violations are not corrected. | 6/11/2020 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | Sight glass on tank leaking oil onto machine room floor creating a trip and fall hazard. Repair or replace as needed. | 7/14/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Oil is leaking onto the machine room floor creating a trip and fall hazard. Clean machine room floor. | 7/14/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post a current state operating certificate in the elevator machine room. | 7/14/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The car door restrictor shall be operational. | 6/29/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 12/4/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 12/4/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)9 | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 12/4/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction to its full height. There is an opening between the second and third landing, that opens into an occupied space. There is also an opening between the first and second landing. | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | When tested, the door restrictor did not work. | 2/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | The hydraulic oil tank located in the machine room is leaking. | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Car door restrictor shall be operational. (2nd Notice) | 2/12/2024 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | Yes | No | Holes in hoistway shall be patched. Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction to its full height. There is an opening between the second and third landing, that opens into an occupied space. There is also an opening between the first and second landing. (2nd Notice) Re-Inspection Required | 2/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | Yes | No | The hydraulic oil tank located in the machine room is leaking. (2nd Notice) Re-Inspection Required | 2/12/2024 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)9 | Yes | No | The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. (2nd Notice) Re-Inspection Required | 2/12/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The lighting in the machine room shall be not less than 10 foot-candles at floor level. | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational on main power and battery back up. | 2/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. | 12/4/2025 |