Inspection
Inspection Details
Equipment ID
25580
25580
Inspection Date
11/21/2025
11/21/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Travis Cardona
Travis Cardona
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
3551a18e-72b6-4165-8dc8-80febea27bc9
3551a18e-72b6-4165-8dc8-80febea27bc9
Location
MLS
326 S 21st St, St. Louis, MO
Phone: (314) 511-2294
Email: pcaldwell@stlcitysc.com
326 S 21st St, St. Louis, MO
Phone: (314) 511-2294
Email: pcaldwell@stlcitysc.com
Owner
Attn: Pharron Caldwell
TKFC LC
1 Center Circle, St. Louis, MO 63103
Phone: (314) 339-0401
Email: pcaldwell@stlcitysc.com
TKFC LC
1 Center Circle, St. Louis, MO 63103
Phone: (314) 339-0401
Email: pcaldwell@stlcitysc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | Emergency communications loss monitor shall work. | 2/22/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Logs are mostly blank. Need all documentation for 2022 & 2023. | 9/12/2024 |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.7.2 Seizing of Rope Ends | No | No | 2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded. They are currently wrapped in electrical tape. | 9/12/2024 |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.5 Wedge Rope Sockets | No | No | 2.20.9.5.4 - Hoist rope tail retaining clips shall be properly spaced. | 9/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Adjust upthrust roller bearings for proper clearance to door hanger track (multiple floors). | 9/12/2024 |
| A17.1-2016 : Elevators | 3.28 - Counterweight and counterweight buffer | 2.21 | No | No | 2.21.1.2 - Counterweight hold down clamps need to be set properly. They are currently 3"- 4" above weight stack. | 9/12/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Take corrective action and re-test. | 12/8/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.19.15 Emergency Communications | Yes | No | 2-WAY COMMUNICATION DEVICE SHALL WORK..Voice works, Camera does not work. | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually. | |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | Counterweight runby does not meet Code Minimum of 6". | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.11.2.1.2(g) | No | No | Non-elevator related items shall not be stored in Machine Room. | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | achine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | MCP - Fire Service must be tested and properly documented monthly on Log Sheet |