Inspection
Inspection Details
Equipment ID
22918
22918
Inspection Date
12/1/2025
12/1/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
319e4da8-eb18-439b-9305-10e7bdf9c44b
319e4da8-eb18-439b-9305-10e7bdf9c44b
Location
Spectrum Retirement Corporation
2929 Dougherty Ferry Rd, St. Louis, MO
Phone: (636) 825-6665
2929 Dougherty Ferry Rd, St. Louis, MO
Phone: (636) 825-6665
Owner
Attn: S-K Dougherty Ferry Owner, LLC
c/o Spectrum Retirement
4600 S Syracuse St, 11th Fl, Denver, CO 80237
Phone: (000) 000-0000
c/o Spectrum Retirement
4600 S Syracuse St, 11th Fl, Denver, CO 80237
Phone: (000) 000-0000
Billing
Attn: AP Lockbox
c/o Spectrum Retirement Communities
PO Box 371710, Denver, CO 80237
Phone: (303) 360-8812
Email: AP@SPECTRUMRETIREMENT.COM
c/o Spectrum Retirement Communities
PO Box 371710, Denver, CO 80237
Phone: (303) 360-8812
Email: AP@SPECTRUMRETIREMENT.COM
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 5/24/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power test was unsuccessful. The elevator shall operate with no load in the car while operating on the emergency generator. | 11/23/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Replace any missing fire tabs on hoistway doors. | 3/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power operation shall be tested. | 3/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. The fire service testing log shall be documented monthly. | 3/16/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | MCP Fire service testing must be properly documented monthly on log sheet. | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1, with identification of the person(s) that performed the operation and the date shall be available on-site. | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power shall be tested. A test was attempted, but the power did not successfully transfer. | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | The disconnecting means (both main and car lighting) shall be marked identifying it as belonging to the elevator with a minimum of 2" in height and of contrasting color to its background. There are 4 disconnects in the machinery space and none are marked to identify what device they feed. | 12/9/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Slide, Gov pullout/pull thru, and gov switch/jaw shall be tested. | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Still requires up to date operating certificate in the machine room. | 3/19/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No up to date State operating certificate in the machine room. |