Inspection
Inspection Details
Equipment ID
9155
9155
Inspection Date
1/18/2019
1/18/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
300
300
Slide
Governor Rope Pull
Door Closing Force
17/15
17/15
External ID
aaaef2cd-e141-4fbd-9ca5-af796035747d
aaaef2cd-e141-4fbd-9ca5-af796035747d
Location
Delhaven Manor
5460 DELMAR BLVD, SAINT LOUIS, MO
5460 DELMAR BLVD, SAINT LOUIS, MO
Owner
Delhaven Manor
5460 DELMAR BLVD, SAINT LOUIS, MO 63112-3104
5460 DELMAR BLVD, SAINT LOUIS, MO 63112-3104
Billing
Attn: Delhaven Manor
5460 DELMAR BLVD, SAINT LOUIS, MO 63112-3104
5460 DELMAR BLVD, SAINT LOUIS, MO 63112-3104
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | x | x | Fireman's stop switch shall work. Reinspect only. Unit was not red-tagged. | 11/1/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Repair inoperative emergency phone. | 7/29/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide maintenance control program and updated monthly elevator fire log. | 3/12/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Provide code compliant machine room lighting (19fc) | 3/12/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 8.11.2.1.2(k) | Provide feeder location for main line and 110v disconnect. | 3/12/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Provide testing of existing emergency battery back-up unit. Written testing procedures are required for maintenance control program. | 9/1/2020 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working, phone line not working. Re-inspection required | 6/8/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | Emergency light shall be operational. | 3/27/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency alarm bell shall be operational. | 3/27/2024 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | x | This elevator is equipped with an overspeed valve and category 5 testing is due. | 3/27/2024 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | x | Doors do not automatically open when battery power is activated. Door operators must be manually reset any time power is lost. | 1/22/2026 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | x | x | The opening of doors shall be on continuous pressure. When pressure is released, doors fail to return to the closed position. | 1/22/2026 |