Inspection
Inspection Details
Equipment ID
6389
6389
Inspection Date
12/6/2025
12/6/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
b93640bd-7b9b-4f12-af24-6d157694e613
b93640bd-7b9b-4f12-af24-6d157694e613
Location
St. Louis Technology Center
587 James S McDonnell Blvd, Hazelwood, MO
Phone: (314) 989-1011
587 James S McDonnell Blvd, Hazelwood, MO
Phone: (314) 989-1011
Owner
Attn: Refinitiv
Refinitiv
587 James McDonnell Blvd, Hazelwood, MO 63042
Phone: (000) 000-0000
Email: facundo.izquierdo@cbre.com
Refinitiv
587 James McDonnell Blvd, Hazelwood, MO 63042
Phone: (000) 000-0000
Email: facundo.izquierdo@cbre.com
Billing
Attn: CBRE Managed Services, Inc
CBRE Managed Services, Inc
2100 Ross Ave, Ste 1600, Dallas, TX 75201
Phone: (000) 000-0000
Email: facundo.izquierdo@cbre.com
CBRE Managed Services, Inc
2100 Ross Ave, Ste 1600, Dallas, TX 75201
Phone: (000) 000-0000
Email: facundo.izquierdo@cbre.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 9/4/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Maintenance control program shall include written procedures for inspections and tests located on site. | 11/3/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current state operating certificate located in machine room. | 11/3/2020 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency power needs to be tested, generators will be tested on bldg on 3/5/22. | 3/5/2022 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV needs to be tested in or less than 90 days | 3/5/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV needs to be tested on or before 4/28/22. Re-inspection required | 8/25/2022 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor is not working. Re-inspection required | 8/19/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 12/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing of emergency generator power operation needs to be scheduled to complete inspection. Re-inspection required | 8/19/2023 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor is not working. Re-inspection required | 8/28/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room. | 12/18/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room | 12/18/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency generator power. Re-inspection required | 2/8/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 12/11/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Perform form the emergency power testing to complete the Cat 1 tests. | 12/11/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.5 Illuminated Visual Signal | Yes | No | Failed Cat 1 firefighters service test. Door hold button did not work, only elevator in building, needs repaired. Re-inspection required |