Inspection
Inspection Details
Equipment ID
13837
13837
Inspection Date
12/4/2025
12/4/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
84bcf44a-d8c0-4576-8456-07ed32175dec
84bcf44a-d8c0-4576-8456-07ed32175dec
Location
Stadium Park West
100 S 9th St, St. Louis, MO
Phone: (314) 241-4262
100 S 9th St, St. Louis, MO
Phone: (314) 241-4262
Owner
Attn: Inter Park Holdings, LLC
Inter Park Holdings, LLC
111 W Jackson Blvd, Ste 1900, Chicago, IL 60604
Phone: (000) 000-0000
Inter Park Holdings, LLC
111 W Jackson Blvd, Ste 1900, Chicago, IL 60604
Phone: (000) 000-0000
Billing
Attn: Property Manager
Inter Park Holdings, LLC
100 S 9th St, St. Louis, MO 63102
Phone: (000) 000-0000
Inter Park Holdings, LLC
100 S 9th St, St. Louis, MO 63102
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Complete category 5 inspection items that still remain (Slide, car & CW buffer, & 125% brake test). | 9/21/2018 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 4/29/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work. | 4/29/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Door closing shall be constant pressure operation on Phase 2 fire service. | 9/21/2018 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Clean the pit. | 4/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | 8.6.4.7.1 - The hoistway shall be kept clean of dirt and rubbish. Clean the hoistway. | 4/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top shall be cleaned. | 4/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | The top and bottom counterweight rollers are worn and require replacement. | 4/29/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator machine room. | 4/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. | 10/23/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Clean the pit. | 10/23/2023 |