Inspection
Inspection Details
Equipment ID
12205
12205
Inspection Date
1/14/2019
1/14/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
William Gorden, Jr.
William Gorden, Jr.
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
28
28
External ID
4a06aa2b-52be-40cb-a458-4fffa33eaabe
4a06aa2b-52be-40cb-a458-4fffa33eaabe
Location
Renaissance Grand Hotel- St. Louis
800 WASHINGTON AVE, SAINT LOUIS, MO
800 WASHINGTON AVE, SAINT LOUIS, MO
Owner
Attn: UNK
Marriott St Louis Grand
800 WASHINGTON AVE, SAINT LOUIS, MO 63101
Phone: (314) 418-5840
Email: karen.hinz@marriott.com
Marriott St Louis Grand
800 WASHINGTON AVE, SAINT LOUIS, MO 63101
Phone: (314) 418-5840
Email: karen.hinz@marriott.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Clean debris from elevator pit. | 1/16/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Clean pit of all rubbish. | 3/9/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 3/9/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 4/7/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light does not work. | 4/7/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two way communication inoperable. Re-inspection required | 3/10/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two way communication phone does not work. Repair or replace and reinspect in 14 days. 3/24/25 | 9/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top shall be kept clean of dust and debris. | 9/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The handrail on the left side and rear of the car are lose. Handrails shall be tightened. A17.1 2016 - 5.8.1.10 | 9/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | One of the traveling cables has electrical tape on likely indicating that there is a break in the exterior protective coating. Replace traveling cable. A17.1 2016 - 5.1.7.1 | 9/30/2025 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | Permanent means of temperature control are inoperable and shall be repaired, or replaced. | 9/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two way communication phone does not work. Repair or replace and reinspect in 14 days. 9/25/2025 | 4/14/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top shall be kept clean of dust and debris. | 4/14/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 4/14/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | Permanent means of temperature control are inoperable and shall be repaired, or replaced. | 4/14/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top shall be kept clean of dust and debris. | |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | Need to replace missing hoistway door restrictor angles as needed. Re-inspection required | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Both traveling cables containing wiring to car have cracks and have worn thru in several places to outer layers of insulation, despite previous repairs. Repair or replace same | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two way communication phone does not work. Repair or replace and reinspect in 14 days | |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | Permanent means of temperature control are inoperable and shall be repaired, or replaced. |