Inspection
Inspection Details
Equipment ID
24712
24712
Inspection Date
11/6/2025
11/6/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
NA
NA
Slide
7.5
7.5
Governor Rope Pull
25/220
25/220
Door Closing Force
Front 23 Rear 22
Front 23 Rear 22
External ID
9fa194fd-ca29-4ccd-a614-1e288eb8f7e2
9fa194fd-ca29-4ccd-a614-1e288eb8f7e2
Location
Element Hotel
3763 Forest Park Ave, St. Louis, MO
Phone: (314) 570-2580
3763 Forest Park Ave, St. Louis, MO
Phone: (314) 570-2580
Owner
Attn: Kathy Prainito
Midas Forest Park I LLC
1804 Borman Circle Dr, St. Louis, MO 63146
Phone: (314) 692-0100
Email: kprainito@MidasHospitality.com
Midas Forest Park I LLC
1804 Borman Circle Dr, St. Louis, MO 63146
Phone: (314) 692-0100
Email: kprainito@MidasHospitality.com
Billing
Attn: c/o ATIS - Certificate Management
Midas Hospitality
600 Emerson Rd, Suite 225, St. Louis, MO 63141
Phone: (314) 441-3983
Email: MidasHospitality@atis.com
Midas Hospitality
600 Emerson Rd, Suite 225, St. Louis, MO 63141
Phone: (314) 441-3983
Email: MidasHospitality@atis.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 8.11.2.1.3(b) | Yes | No | Finish installing light, switch, and GFI in overhead. | 10/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Yes | No | Finish installing light, switch, and GFI in pit. | 10/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | Yes | No | Finish the installation of the sump pump in the pit. | 10/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Seal all penetrations in the hoistway. | 10/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | Yes | No | Finish the installation of the hall walls and install all signage. | 10/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | All phases of fire service shall be tested. | 10/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone and alarm shall be tested. | 10/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.3 Provide Auxiliary Lighting | Yes | No | Emergency lighting shall be tested. | 10/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | Yes | No | All electrical covers shall be installed. | 10/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | Yes | No | Test tags shall be installed on hoist cables. | 10/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 8.11.2.1.1(d) | Yes | No | Finish the installation of the cab flooring. | 10/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 8.11.2.1.1(d) | Yes | No | Grout all sills | 10/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | No | Test tags shall be installed on the governor. | 10/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 8.11.2.1.5(c) | Yes | No | Test tags shall be installed on the buffers. | 10/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.29 - Car and counterweight safeties | 2.17 | Yes | Yes | The safety slide is too short. It should be between 10" and 40" | 10/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.11 - Hoistway smoke control | 2.1.4 | No | No | The powered smoke control vent in the overhead shall automatically open upon detection of smoke in the elevator lobbies or hoistway, upon power failure, and upon activation of a manual override control. | 10/15/2020 |
| A17.1-2016 : Elevators | 4.4 - Hoistway door locking devices | 8.11.2.1.4(d) | Yes | No | Install fire stops on all hoistway doors | 5/2/2022 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(j) | No | No | Provide a ABC rated fire extinguisher within sight of controller on the 7th floor | 5/24/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.6.3 | No | No | Remove prints and maintenance control program from the top of the car & provide a secure container outside the hoistway | 5/24/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | label controller & car sling | 5/24/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Perform monthly fire service and document on log in machine room | 5/24/2022 |