Inspection
Inspection Details
Equipment ID
10684
10684
Inspection Date
12/9/2025
12/9/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
500
500
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
54
54
External ID
46ced9e7-ea4c-4942-b113-74429cdc1c14
46ced9e7-ea4c-4942-b113-74429cdc1c14
Location
Village of Concord Condominiums
10956 Village Grove Dr, St. Louis, MO
Phone: (314) 845-0377
10956 Village Grove Dr, St. Louis, MO
Phone: (314) 845-0377
Owner
Attn: Village of Concord Condo, c/o Efthim Company Realtors
Village of Concord Condo, c/o Efthim Company Realtors
10956 Village Grove Dr, St. Louis, MO 63123
Phone: (314) 845-0377
Village of Concord Condo, c/o Efthim Company Realtors
10956 Village Grove Dr, St. Louis, MO 63123
Phone: (314) 845-0377
Billing
Attn: Efthim Company Realtors
Efthim Company Realtors
4177 Crescent Dr, Ste A, St. Louis, MO 63129
Phone: (314) 845-0377
Email: efthimmgmt@sbcglobal.net
Efthim Company Realtors
4177 Crescent Dr, Ste A, St. Louis, MO 63129
Phone: (314) 845-0377
Email: efthimmgmt@sbcglobal.net
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current state operating certificate. | 12/13/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 3/25/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | A code data plate shall be provided. | 3/25/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | The infrared door re-opening device (light ray) shall be overridden on all phases of fire service. - 14 days to correct violation - Not red tagged. This unit is the only elevator in the building. | 3/19/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 12/8/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 8/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. Note: A dial tone is present, the phone dials out, but immediately hangs up. Two way communication couldn't be established. | 2/23/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | The car shall return to the egress floor on Phase 2 fire service with the doors in the normal open position and the phase 2 key-switch in the off position. This elevator was not red tagged due to being the only elevator in the building. | 2/23/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | The car shall return to the egress floor on Phase 2 fire service with the doors in the normal open position and the phase 2 key-switch in the off position. | 7/9/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Phase II fire service is not working properly. Door hold button does not work and shall be repaired. |