Inspection
Inspection Details
Equipment ID
11871
11871
Inspection Date
12/10/2025
12/10/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Chad Hackstadt
Chad Hackstadt
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
NA
NA
Slide
Softset
Softset
Governor Rope Pull
NA
NA
Door Closing Force
26
26
External ID
cb85489f-7e74-4aae-8046-6023b3a1711e
cb85489f-7e74-4aae-8046-6023b3a1711e
Location
The Dorchester
665 S Skinker Blvd, St. Louis, MO
Phone: (314) 721-8181
665 S Skinker Blvd, St. Louis, MO
Phone: (314) 721-8181
Owner
Attn: The Dorchester
The Dorchester
665 S Skinker Blvd, St. Louis, MO 63105
Phone: (816) 759-0525
Email: STLManager@macapartments.com
The Dorchester
665 S Skinker Blvd, St. Louis, MO 63105
Phone: (816) 759-0525
Email: STLManager@macapartments.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 9/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.11.2.3.1 | Yes | Yes | A category 5 full load test shall be scheduled in the 2019 calendar year. | 9/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.3.2 | Yes | No | A category 5 full load test shall be scheduled in the 2019 calendar year. | 9/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 8.11.2.3.6 | Yes | No | A category 5 full load test shall be scheduled in the 2019 calendar year. | 9/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 8.11.2.1.3(z) | No | No | Provide shortening of the governor rope. | 2/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.27 - Rope fastenings | 8.11.2.1.2(y) | No | No | The wire-rope retaining clips shall be properly installed. At least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope (see Figure 2.20.9.5). The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. | 1/5/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 8.11.2.1.2(k) | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 1/5/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency phone does not work. Initiate the necessary corrective action. | 12/28/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 1/26/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP, including PM records and monthly fire service test log, not being properly documented. | 2/28/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | Suspension rope tensions shall be substantially equalized. | 2/28/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Remove excess debris. | 2/28/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. 2022 MCP records are missing. | 2/28/2024 |