Inspection
Inspection Details
Equipment ID
13626
13626
Inspection Date
12/18/2025
12/18/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Douglas Miller
Douglas Miller
Relief Valve Pressure
400
400
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
24
24
External ID
4702146d-7f7b-4e9a-aae0-7073ead255e3
4702146d-7f7b-4e9a-aae0-7073ead255e3
Location
Flowers Hall
209 S Kingshighway St, St. Charles, MO
Phone: (000) 000-0000
209 S Kingshighway St, St. Charles, MO
Phone: (000) 000-0000
Owner
Attn: Joyce Norman
Lindenwood University
209 S Kingshighway St, St. Charles, MO 63301
Phone: (636) 949-4922
Alt Phone: (636) 579-1235
Email: JNorman@lindenwood.edu
Lindenwood University
209 S Kingshighway St, St. Charles, MO 63301
Phone: (636) 949-4922
Alt Phone: (636) 579-1235
Email: JNorman@lindenwood.edu
Billing
Attn: Accounts Payable
Lindenwood University
209 S Kingshighway St, St. Charles, MO 63301
Phone: (636) 949-4922
Alt Phone: (636) 579-1235
Email: AccountsPayable@lindenwood.edu
Lindenwood University
209 S Kingshighway St, St. Charles, MO 63301
Phone: (636) 949-4922
Alt Phone: (636) 579-1235
Email: AccountsPayable@lindenwood.edu
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Car emergency telephone shall work. | 12/19/2019 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Car door restrictor shall work. | 12/19/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The in car emergency light shall be operational. | 2/20/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency alarm bell shall operate with 110v source removed. | 2/20/2020 |
| A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | No | No | The car operating panel (COP) shall be secured. - Re-Inspection Required | 1/2/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | An MCP shall be in place as specified in A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 | 1/7/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | The car station fire visual indication/call cancel button shall be marked as specified in A17.1 1996 - 306.11 and 211.3. This violation shall be corrected in 14 days. ( This indicator/button had been replaced with an unmarked button) | 12/18/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 1/31/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 1/31/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 1/28/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. Based on the installation year of 2004, a category 5 test is due on the overspeed valve on or before the next annual inspection. | 1/9/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/29/2024 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 207.4 | No | No | The car handrail is missing and shall be replaced. | 1/21/2026 |