Inspection
Inspection Details
Equipment ID
12585
12585
Inspection Date
1/16/2019
1/16/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Mark Brown
Mark Brown
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
dc15d1d9-a2ce-4579-9d88-b472642ab598
dc15d1d9-a2ce-4579-9d88-b472642ab598
Location
Continental Life Bldg
3615 OLIVE ST, SAINT LOUIS, MO
3615 OLIVE ST, SAINT LOUIS, MO
Owner
Fidelity Associates
120 S CENTRAL AVE STE 500, SAINT LOUIS, MO 63105-1733
120 S CENTRAL AVE STE 500, SAINT LOUIS, MO 63105-1733
Billing
Attn: Fidelity Associates
120 S CENTRAL AVE STE 500, SAINT LOUIS, MO 63105-1733
120 S CENTRAL AVE STE 500, SAINT LOUIS, MO 63105-1733
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperable alarm bell. | 7/10/2019 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Repair inoperative door restrictor. | 2/19/2020 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Replace missing door gibbs 21st and 7th floors | 5/12/2021 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Replace defective hoist cables due to heavy rouge and diameter reduction by 1/20/20 | 2/19/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | Fire recall buzzer inoperative. | 4/23/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 4/23/2021 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Replamp machine room lighting fixtures above machines. | 5/12/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Need light above controller | 1/27/2022 |
| A17.1-2016 : Elevators | 1.12 - Car enclosure | 8.11.2.1.1(l) | No | No | Iron on cab walls needs to be secured | 1/27/2022 |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.11.2.1.3(w) | No | No | Fire tabs on door hangers | 1/27/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Dust covers in machine room | 1/27/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Exposed live wiring on brake switches | 1/27/2022 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.11.2.1.2(ff) | Yes | Yes | Govenor test failed, Red tagged elevator | 1/27/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vison plate over it. | 12/31/2024 |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.11.2.1.3(w) | Yes | No | Upper hoistway door hanger safety retainers are defeated/turned down on almost all doors. Shall be corrected. (Previously Cited Violation) | |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | Counterweight runby, 1.5", does not meet Code Requirements. Shorten cables | |
| A17.1-2016 : Elevators | 1.16 - Rated load, platform area, and data plate | 2.16.5 | No | No | COP shall have car number displayed, 0.5" lettering. | |
| A17.1-1996 : Elevators | 3.27 - Crosshead data plate | 212.2 | No | No | Suspension ropes shall have proper data tag(s) | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean. Remove excess debris |