Inspection
Inspection Details
Equipment ID
22447
22447
Inspection Date
12/16/2025
12/16/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
NA
NA
Slide
4 1/2"
4 1/2"
Governor Rope Pull
40/120
40/120
Door Closing Force
22
22
External ID
64f74a4e-0d19-4c37-a187-5316728023df
64f74a4e-0d19-4c37-a187-5316728023df
Location
The Standard
3853 Forest Park Ave, St. Louis, MO
Phone: (314) 565-4411
Email: athenac@landmarkproperties-leasing.com
3853 Forest Park Ave, St. Louis, MO
Phone: (314) 565-4411
Email: athenac@landmarkproperties-leasing.com
Owner
Attn: Jack Simpson
The Standard
3853 Forest Park Ave, St. Louis, MO 63108
Phone: (314) 534-9248
Email: jack.simpson@landmarkproperties.com
The Standard
3853 Forest Park Ave, St. Louis, MO 63108
Phone: (314) 534-9248
Email: jack.simpson@landmarkproperties.com
Billing
Attn: Jack Simpson
The Standard
3853 Forest Park Ave, St. Louis, MO 63108
Phone: (314) 534-9248
Email: jack.simpson@landmarkproperties.com
The Standard
3853 Forest Park Ave, St. Louis, MO 63108
Phone: (314) 534-9248
Email: jack.simpson@landmarkproperties.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Need copy of current state operating certificate in machine room. | 5/10/2019 |
| conversion | conversion | n/a | No | No | Remove water from pit. | 5/10/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Could not establish two-way communication. | 4/24/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | Make belt monitor operational. | 5/10/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 5/10/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 7/2/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Remove the water from the pit. The pit shall be kept dry. | 2/22/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 7/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | Provide proper machine room ventilation. | 9/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current State operating certificate shall be displayed in the machine room in a non-combustible frame with a clear cover. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Repair broken lense on the emergency ligting. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Provide signage indicating the source of feed for mainline and 110 volt disconnects in control space. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.16.8 | Yes | No | Automatic return unit not functioning posing a possible entrapment in the event of building power loss. |