Inspection
Inspection Details
Equipment ID
13424
13424
Inspection Date
12/29/2025
12/29/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
380
380
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
20
20
External ID
8b20e490-79f0-40eb-8393-a1df0a1374cd
8b20e490-79f0-40eb-8393-a1df0a1374cd
Location
McCormack House
3915 Olive St, St. Louis, MO
Phone: (314) 531-8844
3915 Olive St, St. Louis, MO
Phone: (314) 531-8844
Owner
Attn: Jill Richards
House at Westminster
3915 Olive St, St. Louis, MO 63108
Phone: (314) 488-7504
Email: jrichards@broadmg.com
House at Westminster
3915 Olive St, St. Louis, MO 63108
Phone: (314) 488-7504
Email: jrichards@broadmg.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide on-site maintenance control program. | 7/24/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency battery lowering device does not work. | 3/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | One bulb in emergency light does not work. | 3/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | When unit was put on ring, excessive fluid leakage from top Vic fitting (below valve) or bottom of valve. Repair as needed. | 7/24/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be properly displayed in machine room. | 7/24/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Replace bad light bulb in emergency light fixture. Reinspect required. | 8/11/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall provide two way communications, no one answered. Reinspect required. | 8/11/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Battery lowering system shall work. Reinspect required. | 8/11/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 9/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Need to replace bad light bulb in emergency light fixture. Re-inspection required | 10/24/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall provide two way communication. Re-inspection required | 10/24/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 11/8/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 5/15/2024 |
| A17.1-1996 : Elevators | 2.32 - Control Valve | 303 | Yes | No | Car failed 15 minute stand test, technician determined that it is leaking back through the valve. | 3/27/2025 |