Inspection
Inspection Details
Equipment ID
18764
18764
Inspection Date
1/15/2019
1/15/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
26
26
External ID
b7e2e650-7c46-47c5-ad2c-e1d78e1439b7
b7e2e650-7c46-47c5-ad2c-e1d78e1439b7
Location
Lumiere Place Casino
999 N 2ND ST, SAINT LOUIS, MO
999 N 2ND ST, SAINT LOUIS, MO
Owner
Attn: Dwight Buchannon
Four Seasons Hotel
999 N 2ND ST, SAINT LOUIS, MO 63102
Phone: (314) 498-8304
Email: dwight.buchannon@fourseasons.com
Four Seasons Hotel
999 N 2ND ST, SAINT LOUIS, MO 63102
Phone: (314) 498-8304
Email: dwight.buchannon@fourseasons.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Repair bent safety actuating link rod on car crosshead. (Governor sheave gauge bottoms on "C" measurement). | 1/15/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm button on Main COP not working. | 11/18/2019 |
| A17.1-1996 : Elevators | 2.29 - Car and counterweight safeties | 1002.2b | Yes | Yes | Safety rod bent on top of the elevator. Did NOT red tag. Reinspect only. | 11/18/2019 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1200.4d | Yes | No | Suspension belts showing rouge. Monitor shows replacement. Replace belts in 60 days. | 11/18/2019 |
| A17.1-1996 : Elevators | 2.29 - Car and counterweight safeties | 1002.2b | Yes | Yes | Repair bent safety actuating link rod on car crosshead. | 1/22/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Coated steel belt monitor communication disabled. Communication re-established but no maintenance records found of this, or any other event, in elevator equipment room. Provide unit maintenance records. | 12/8/2025 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.11.2.1.3(cc) | Yes | No | Belt monitor showing bad belts, Unit turned off. Re-inspection required | 5/31/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire Service Phase 1 & 2 must be tested, Re-inspection required | 5/31/2023 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 | No | No | door to access pit equipment shall be lockable to prevent access by non elevator personnel | 12/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm shall work | 7/22/2024 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 2.18.1 | Yes | Yes | Overspeed governor exceeded maximum allowable pull through measurement. Red tagged. Replace governor and governor rope and retest | 7/22/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Coated steel belt monitor communication was disabled. Communication was re-established, but no maintenance records found of this or any other event in elevator machine room. provide unit maintenance records | 12/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform the following tests to complete 5 year inspection: car safeties, car buffer, counterweight buffer, 125% brake, unintended movement | 7/22/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | Yes | Yes | The hoist belt monitoring system is disabled with visible rouge present on the hoist belts. The hoist belts shall be replaced with the hoist belt monitoring being re-enabled with an alteration permit being issued and a reinspection performed before the elevator shall be returned to service. | 6/5/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform the following tests to complete 5 year inspection: car safeties, car buffer, counterweight buffer, 125% brake, unintended movement | 6/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm shall work. | 6/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 Access to Pit | No | No | door to access pit equipment shall be lockable to prevent access by non elevator personnel | 12/8/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Means of two-way communication are inoperable and shall be repaired, or replaced. | 12/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Fire service Phase I operation instructions in main lobby are rubbed off, need to replace signage. | 12/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | T Cable showing signs of wear. Repair or replace. | 12/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | Pit light not working | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone not working |