Inspection
Inspection Details
Equipment ID
2065
2065
Inspection Date
10/1/2025
10/1/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Major Davis
Major Davis
Mechanic Name
Jason Stout
Jason Stout
Relief Valve Pressure
NA
NA
Slide
420
420
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
d8f7044c-8dda-4188-9249-9c8dec99f03e
d8f7044c-8dda-4188-9249-9c8dec99f03e
Location
Hillyard Industries
302 N 4th St, St. Joseph, MO
Phone: (816) 233-1321
302 N 4th St, St. Joseph, MO
Phone: (816) 233-1321
Owner
Attn: Hillyard Industries
Hillyard Industries
402 N 3rd St, St. Joseph, MO 64501
Phone: (000) 000-0000
Hillyard Industries
402 N 3rd St, St. Joseph, MO 64501
Phone: (000) 000-0000
Billing
Attn: Hillyard Industries
Hillyard Industries
PO Box 909, St. Joseph, MO 64502
Phone: (000) 000-0000
Alt Phone: (816) 262-8731
Email: KKing@Hillyard.com
Hillyard Industries
PO Box 909, St. Joseph, MO 64502
Phone: (000) 000-0000
Alt Phone: (816) 262-8731
Email: KKing@Hillyard.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.16 - Rated load, platform area, and data plate | 1001.2(a)(16) | No | No | Need to post "C-1 Loading No Passenger" sign inside elevator. | 1/16/2026 |
| A17.1-1996 : Elevators | 1.16 - Rated load, platform area, and data plate | 1001.2(a)(16) | No | No | Need to post "C-1 Loading No Passengers" sign inside elevator. Lettering to be a minimum of 1/2 inch high. | 1/16/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly | 1/16/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter operating instructions next to hall fire keyswitch | 1/16/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Post emergency evacuation of passengers form inside machine room | 1/16/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate inside machine room | 1/16/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 9/22/2021 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Car emergency light does not operate | 9/22/2021 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Remove debris from pit | 1/16/2026 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | Post code data plate "A17.1 1996" on controller or disconnect. | 1/16/2026 |
| A17.1-1996 : Elevators | 1.16 - Rated load, platform area, and data plate | 207 | No | No | Post sign on elevator. "C-1 LOADING. THIS ELEVATOR DESIGNED TO TRANSPORT LOADED INDUSTRIAL TRUCK. MAXIMUM COMBINED WEIGHT OF INDUSTRIAL TRUCK AND LOAD NOT TO EXCEED 10000 LB" | 1/16/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | No | No | All elevators in the same building shall have firefighter keyswitches keyed the same. | 9/13/2022 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light does not illuminate | 9/13/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 9/13/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | No | No | All elevators in the same building shall have firefighter keyswitches operated by the same key. | 9/13/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Remove debris from the elevator pit. | 1/16/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly. | 1/16/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room. | 1/16/2026 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Machine room access door needs to be self-locking | 1/16/2026 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light does not illuminate | 9/12/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 9/12/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed in machine room | 1/16/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | Yes | No | Firefighter keyswitches shall be operable using the same key as the other elevators in the building | 9/12/2023 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a | No | No | Repair holes in machine room ceiling to maintain fire rating of the machine room. | 1/16/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No maintenance control plan in the machine room | 1/16/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance record log in the machine room | 1/16/2026 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Machine room access door shall be self-locking and non-defeatable | 1/16/2026 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a | No | No | Repair penetrations in machine room cieling. | 1/16/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No MCP | 1/16/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance records on site | 1/16/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 1/16/2026 |