Inspection
Inspection Details
Equipment ID
79
79
Inspection Date
1/16/2026
1/16/2026
Inspection Type
Reinspection
Reinspection
Inspector Name
Dennis Smith
Dennis Smith
Mechanic Name
Jason Stout
Jason Stout
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
15
15
External ID
d04eabdf-aae3-4599-b216-92125df1a45d
d04eabdf-aae3-4599-b216-92125df1a45d
Location
Mosaic Medical Center-Maryville
2016 S Main St, Maryville, MO
Phone: (660) 562-2600
2016 S Main St, Maryville, MO
Phone: (660) 562-2600
Owner
Attn: Ryan Rush, MHA
Mosaic Medical Center-Maryville
2016 S Main St, Maryville, MO 64468
Phone: (816) 271-6816
Alt Phone: (816) 646-3013
Email: Ryan.Rush@mymlc.com
Mosaic Medical Center-Maryville
2016 S Main St, Maryville, MO 64468
Phone: (816) 271-6816
Alt Phone: (816) 646-3013
Email: Ryan.Rush@mymlc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 9/2/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Provide means to disconnect car lighting in machine room. Existing disconnect has been bypassed. | 2/22/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | Label machine room equipment with identification that corresponds to identification inside the elevator and the car crosshead. | 11/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Identify inside of doors with a numeral corresponding to landing floor. Numeral to be a minimum of 4 inches tall. | 11/16/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test emergency standby operation with an inspector present. | 8/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide "Elevator Emergency Power" signal in the lobby at the designated landing | 9/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate without normal power | 11/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 (Re-Inspection) | Yes | No | Replace pit sprinkler head with sidewall sprinkler head located within 24 inches from pit floor | 11/21/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Test emergency power with inspector present | 11/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 2.13.4.2.3 | Yes | No | FRONT DOOR TORQUE IS >30lbs | 1/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.3 - Final and emergency terminal stopping devices | 2.25.3 | Yes | Yes | UP LIMIT NOT WORKING BEFORE WE HIT THE STOP RING | 1/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | IN CAR EMERGENCY PHONE IS WORKING UNDER NORMAL CONDITIONS BUT NOT WORKING ON BATTERY BACK-UP | 1/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | CAR DOOR DOES NOT STAY OPEN ON PHASE 2 FIRE SERVICE | 1/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | IN CAR PHONE IS WORKING UNDER NORMAL POWER CONDITIONS BUT NOT WORKING UNDER BATTERY BACKUP CONDITIONS | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | CAR DOORS WILL NOT STAY OPEN DURING PHASE 2 FIRE SERVICE |