Inspection
Inspection Details
Equipment ID
20987
20987
Inspection Date
1/20/2026
1/20/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
5441003e-7722-4e76-a59d-6447e8cceade
5441003e-7722-4e76-a59d-6447e8cceade
Location
ARCO Office Building
900 N Rock Hill, St. Louis, MO
Phone: (314) 963-0715
900 N Rock Hill, St. Louis, MO
Phone: (314) 963-0715
Owner
Attn: ARCO
ARCO
900 N Rock Hill, St. Louis, MO 63119
Phone: (417) 883-4333
Email: abinnington@arco.com
ARCO
900 N Rock Hill, St. Louis, MO 63119
Phone: (417) 883-4333
Email: abinnington@arco.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired | 1/20/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide MCP. | 1/20/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV is due for full load test and tripping speed checked. Re-inspection required | 2/16/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lights in cab do not work, needs repaired. Re-inspection required | 2/16/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | Yes | Emergency lowering is not working. Red-tagged, Re-inspection required | 4/29/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 4/29/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm is not working. Re-inspection required | 4/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting is not working. Re-inspection required | 4/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired, have serviced or replaced | 1/20/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency lowering shall be made operational. Re-inspection required | 2/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light is not operational. Re-inspection required | 2/3/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm shall be made operational. Re-inspection required | 2/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 1/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Provide alarm bell to work. | 1/20/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Provide existing emergency lights and bell to work properly. | 1/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired. |