Inspection
Inspection Details
Equipment ID
8834
8834
Inspection Date
1/12/2026
1/12/2026
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
NA
NA
Slide
28"
28"
Governor Rope Pull
100/900
100/900
Door Closing Force
23
23
External ID
9edbe185-4369-421e-8493-deb07572c925
9edbe185-4369-421e-8493-deb07572c925
Location
Gallery 720
720 Olive St, St. Louis, MO
Phone: (314) 436-1711
720 Olive St, St. Louis, MO
Phone: (314) 436-1711
Owner
Attn: M. Shapiro Real Estate Group
M. Shapiro Real Estate Group
720 Olive St, Apt 2720, St. Louis, MO 63101
Phone: (314) 436-1711
Fax: (314) 436-7348
Email: manager@rentgallery720.com
M. Shapiro Real Estate Group
720 Olive St, Apt 2720, St. Louis, MO 63101
Phone: (314) 436-1711
Fax: (314) 436-7348
Email: manager@rentgallery720.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | No | No | All machine room wiring shall be code compliant with NEC. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Provide code compliant lighting (19ftc) in the machine room. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Provide code compliant GFCI type receptacles in machine room. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Provide code compliant lighting (10ftc) through-out the pit. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide correct information on phone message. Message has the wrong car number. | 1/27/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.40 - Maintenance Records | 2.26.1.4 Inspection Operation | No | No | 8.6.4.9 - Clean the car top. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Provide a working door restrictor. | 1/27/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Provide code compliant lighting(19 ftc) in the secondary machine space. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.7.1.8 | No | No | Provide a code date plate on the controller including information pertaining to the major alteration. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.40 - Maintenance Records | n/a | No | No | Provide MCP. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | No | No | All machine room wiring shall be enclosed. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 8.11.2.1.3(r) | No | No | Hoistway ducts shall have covers installed. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc)(1) Wire ropes shall be replaced | Yes | Yes | The hoist ropes are rouged and approaching minimum diameter and shall be replaced. | 3/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post the current state operating certificate in the elevator machine room. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide MCP documentation. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys (Re-Inspection) | Yes | No | Phase 1 fire service key switch shall be operational in the firemans command panel. | 3/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | Provide code compliant pit lighting. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | No | No | All machine room wiring shall be enclosed. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 8.11.2.1.3(r) | No | No | Hoistway ducts shall have covers installed. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection) | Yes | No | The hoist ropes are rouged and approaching minimum diameter and shall be replaced. | 10/6/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post the current state operating certificate in the elevator machine room. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide MCP. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | Provide code compliant pit lighting. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | The main disconnect shall be labeled with the source location, name, and breaker numbers. | 5/3/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including onsite documents. | 5/3/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 5/3/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The car door restrictor shall be operational. | 5/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | The machine room door shall be self-closing and self-locking. | 5/3/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service test charts are missing. | 12/19/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | The machine room door shall be self-closing and self-locking. | 12/19/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Yes | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 8/19/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.26.4 | Yes | No | The main disconnect shall be labeled with the source location, name, and break numbers. | 8/19/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 1/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service testing must be documented monthly. No documentation in the machine room. | 1/27/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept free of dirt and rubbish and shall not be used for storage purposes |