Inspection
Inspection Details
Equipment ID
7192
7192
Inspection Date
1/19/2026
1/19/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Amador
Michael Amador
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
24
24
External ID
00046271-28f1-45ad-bf72-408db19cae4e
00046271-28f1-45ad-bf72-408db19cae4e
Location
St Louis Union Station Hotel (Hilton)
1820 Market St, St. Louis, MO
Phone: (314) 802-3150
1820 Market St, St. Louis, MO
Phone: (314) 802-3150
Owner
Attn: Lodging Hospitality Management
Lodging Hospitality Management
111 Westport Plz, Ste 500, St. Louis, MO 63146
Phone: (314) 802-3153
Email: mhutchinson@stlunionstationhotel.com
Lodging Hospitality Management
111 Westport Plz, Ste 500, St. Louis, MO 63146
Phone: (314) 802-3153
Email: mhutchinson@stlunionstationhotel.com
Billing
Attn: Lodging Hospitality Management
Lodging Hospitality Management
111 Westport Plz, Ste 500, St. Louis, MO 63146
Phone: (314) 802-3153
Email: aputnam@lhmc.com
Lodging Hospitality Management
111 Westport Plz, Ste 500, St. Louis, MO 63146
Phone: (314) 802-3153
Email: aputnam@lhmc.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Phase II operation not working properly | 1/28/2019 |
| conversion | conversion | n/a | No | No | Only pipes wiring and duct used in connection with the elevator can be in hoist way | 1/23/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | Yes | Broken rope lays disconnected on number 3 cable. Re-rope car and redo safety test. | 2/1/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Lighting in elevator cab shall be guarded to prevent breakage. | 1/15/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | Provide means to lock cartop emergency exit. | 1/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Emergency stop switch in cab is not fastened (broken). | 1/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair alarm bell. | 11/12/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Place current state operating certificate in elevator machine room. | 1/15/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Remove and reroute temporary low and high voltage wiring at machine space above hoistway. Shall comply with NFPA 70. | 1/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Light ray door protection not installed on its own circuit. Reconnect light ray to door protection circuit. | 1/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair flexible conduit to car top lighting. | 1/7/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | The elevator hoistway shall be fully enclosed as follows: Enclosures shall be unperforated to a height of 6 ft above each floor or landing and above the treads of adjacent stairways. Unperforated enclosures shall be so supported and braced as to deflect not over 1" when subjected to a force of 100 lbs applied horizontally to any point, Open work enclosures may be used above the 6 ft level and shall reject a ball 2" in diameter. Machine room next to machine | 1/27/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Elevator hoisting ropes are showing a high degree of wear and shall be replaced, replace ropes within 30 days of inspection | 3/25/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Low voltage coaxial cable has been installed in hoistway, only items relating to the operation of the elevator are allowed to be installed in the hoistway, remove coaxial cable | 1/27/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit is covered in water, the pit shall be kept clean & dry | 1/27/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the elevator machine room. | 1/27/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Low voltage coaxial cable has been installed in the elevator hoistway, only items related to the operation of the elevator are allowed to be installed in the elevator hoistway, need to remove coaxial cable from the hoistway. | 1/27/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | When on Phase II, car opens with pressing the door opens, but does not immediately close, when the door open button is released, needs repaired. Re-inspection required | 3/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Cartop inspection station up button needs to work | 1/27/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/27/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Low voltage coaxial cable has been installed in the elevator hoistway, only items related to the operation of the elevator are allowed to be installed in the elevator hoistway. Remove coaxial cable from the hoistway. | 1/27/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Low Voltage coax cable in hoistway shall be removed. | 3/26/2026 |