Inspection
Inspection Details
Equipment ID
26738
26738
Inspection Date
1/8/2026
1/8/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Joseph Ammons
Joseph Ammons
Relief Valve Pressure
n/a
n/a
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
20
20
External ID
da692352-cebe-4e7b-85d5-9931b5c6e76d
da692352-cebe-4e7b-85d5-9931b5c6e76d
Location
The Kitchen Mixed Use Building
1300 Woodrail Ave, Columbia, MO
Phone: (573) 289-4610
Email: matt.hollrah@tykheconstruction.com
1300 Woodrail Ave, Columbia, MO
Phone: (573) 289-4610
Email: matt.hollrah@tykheconstruction.com
Owner
Attn: Adam Patchett
P1316 LLC
4240 Philips Farm, Ste 109, Columbia, MO 65201
Phone: (000) 000-0000
Email: matt.hollrah@tykheconstruction.com
P1316 LLC
4240 Philips Farm, Ste 109, Columbia, MO 65201
Phone: (000) 000-0000
Email: matt.hollrah@tykheconstruction.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | Yes | No | Pit sump pump is required and shall have the capacity to remove a minimum of 3,000 gal/h per elevator (allowing for head pressure resulting from discharge piping height). | 12/16/2024 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Machine room lighting shall not be less than 19fc at floor. | 12/16/2024 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Spaces containing machines, control equipment, sheaves, and other machinery shall be separated from the remainder of the building by a fire-resistive enclosure. Seal hoistway holes and penetrations with approved fire resistant material. | 12/16/2024 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | Knockout plugs missing on multiple electrical boxes at the top of the hoistway. | 12/16/2024 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | Top of the hoistway has a "flex" electrial run longer than 6' of continuous run. | 12/16/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | Yes | No | Pit sump pump discharge piping shall be of fire-resistant/non-combustible materials. All materials contained within the hoistway shall meet minimum fire-resistance rating. | 12/16/2024 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | Pit electrical piping shall be of fire-resistant/non-combustible materials. All materials contained within the hoistway shall meet minimum fire-resistance rating. | 12/16/2024 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 3.26.1 | Yes | No | Disconnects do not meet 30" rule/not co-planer (electrical supply). | 12/16/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Heat devices did not initiate shunt and smokes did not initiate proper floor recalls or Hat operation. | 12/16/2024 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | No | No | One knockout plug missing at the top of hoistway. | 1/31/2026 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.11.2.1.2(ii) | No | No | PBOE (auxillary battery system for drifting car for passenger evacuation), not working, repair and retest. |