Inspection
Inspection Details
Equipment ID
1162
1162
Inspection Date
1/21/2026
1/21/2026
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Joseph Ammons
Joseph Ammons
Relief Valve Pressure
n/a
n/a
Slide
12"
12"
Governor Rope Pull
90/500
90/500
Door Closing Force
22
22
External ID
f835752e-dd47-4f81-8401-0e611c7d151b
f835752e-dd47-4f81-8401-0e611c7d151b
Location
Truman Building
301 W High St, Jefferson City, MO
Phone: (573) 522-5614
Email: haley.barron@oa.mo.gov
301 W High St, Jefferson City, MO
Phone: (573) 522-5614
Email: haley.barron@oa.mo.gov
Owner
Attn: State of Missouri-INTERAGENCY
State of Missouri-INTERAGENCY
301 W High St, Ste 730, Jefferson City, MO 65101
Phone: (573) 694-8690
Alt Phone: (573) 751-6329
Email: fmdcmail@oa.mo.gov
State of Missouri-INTERAGENCY
301 W High St, Ste 730, Jefferson City, MO 65101
Phone: (573) 694-8690
Alt Phone: (573) 751-6329
Email: fmdcmail@oa.mo.gov
Billing
Attn: INTERAGENCY
OA- FMDC-HST RM 730-INTERAGENCY
PO Box 809, Jefferson City, MO 65102
Phone: (573) 751-0920
OA- FMDC-HST RM 730-INTERAGENCY
PO Box 809, Jefferson City, MO 65102
Phone: (573) 751-0920
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Shorten ropes, no runby present. | 2/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Provide maintenance on all landing door assemblies, rollers, upthrust, etc. All comonents in need of maintenance. | 2/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top. | 1/31/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 1/31/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Clean machine room. | 1/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP in machine room. | 1/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Provide monthly FFS testing log in machine room. | 1/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | Yes | No | Emergency power not tested at time of inspection. | 2/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP in machine room. | 1/31/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 1/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.27 - Rope fastenings | 8.11.2.1.2(y) | No | No | Counterweight shackles missing anti spin device. | 1/31/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 1/31/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Emergency power not tested at time of inspection. | 1/10/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace worn hoisting ropes. | 1/23/2025 |