Inspection
Inspection Details
Equipment ID
181
181
Inspection Date
1/14/2019
1/14/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Richard Rickermann
Richard Rickermann
Relief Valve Pressure
620
620
Slide
Governor Rope Pull
Door Closing Force
22F/28R
22F/28R
External ID
c5e28f68-804b-4a71-803a-0beece7f4f05
c5e28f68-804b-4a71-803a-0beece7f4f05
Location
Seckman High School
2800 SECKMAN RD, IMPERIAL, MO
2800 SECKMAN RD, IMPERIAL, MO
Owner
Fox C-6 School District
745 JEFFCO BLVD, ARNOLD, MO 63010-1432
745 JEFFCO BLVD, ARNOLD, MO 63010-1432
Billing
Attn: Fox C-6 School District
745 JEFFCO BLVD, ARNOLD, MO 63010-1432
745 JEFFCO BLVD, ARNOLD, MO 63010-1432
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. | |||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | Battery lowering device does not work per code. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10. | 12/8/2022 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | The machine room door shall be self-closing. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Install a code data plate. It shall read: Missouri Minimums. | |||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Phase 1 & 2 key switches worked intermittently. Could not perform test properly. Take corrective action and perform a successful fire service test. | 12/8/2022 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Up to date operating certificate required in the machine room. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | |||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Auxiliary power lowering does not work. Take corrective action and re-test. | 1/14/2025 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Missing handrail inside car. | |||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Fireman's key switch needs to be replaced. | 1/14/2025 | |
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Fireman's key switch needs to be replaced. (2nd Notice) | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | Auxiliary power lowering does not work. Take corrective action and re-test. (2nd Notice) |