Inspection
Inspection Details
Equipment ID
12065
12065
Inspection Date
1/17/2019
1/17/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
12"
12"
Governor Rope Pull
60/380
60/380
Door Closing Force
21
21
External ID
cb882c9c-9b70-498b-9690-2630e0f6a2d5
cb882c9c-9b70-498b-9690-2630e0f6a2d5
Location
Curlee Building
611 N 10TH ST, SAINT LOUIS, MO
611 N 10TH ST, SAINT LOUIS, MO
Owner
Southland 2015-SPC4 REOI, LLC
8115 PRESTON RD STE 500, DALLAS, TX 75225-6334
8115 PRESTON RD STE 500, DALLAS, TX 75225-6334
Billing
Attn: Forsite reality Management
5600 N RIVER RD STE 925, ROSEMONT, IL 60018-5112
5600 N RIVER RD STE 925, ROSEMONT, IL 60018-5112
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The fire extinguisher in the machine room shall be serviced (Expired 2016). | 3/18/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing. | 3/18/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 3/18/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | No | No | Pipes conveying liquid are not permitted in the hoistway. | 3/18/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair the pit lighting. | 3/18/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)8 | No | No | Egress shall not be blocked by door at 7th floor. | 3/18/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | In car emergency stop switch shall be overridden on Phase 1 fire service. | 2/10/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room shall have a self-closing and self-locking door and shall operable from the interior space without the use of a key. | 3/18/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/18/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational on auxiliary power. | 8/25/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | The counterweight guard shall extend from a point not more than 12" above the pit floor. | 3/18/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The in car lighting shall be guarded. | 3/18/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | No | No | Pipes conveying liquids, gases, or vapors shall not be located in the hoistway. The copper pipe in the overhead shall be removed. | 3/18/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit lighting shall be operational. | 3/18/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Phase 2 fire service shall be operational. (Violation to be corrected no later than April 17th, 2020. | 8/25/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | The wireway feeding the car and counterweight buffer switches has rusted away and has energized wires exposed that shall be replaced. | 3/18/2021 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | A hoist rope tag shall be provided. | 3/18/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The counterweight is compressing the buffer with the car level at the top landing. Counterweight runby shall be provided. | 3/18/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Hoistways containing passenger elevators shall be fully enclosed and the enclose shall be of a solid construction. The large hole through the back hoistway wall in the pit looking into a restroom shall be repaired. | 3/18/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The car and counterweight buffer switches shall be operational. | 8/25/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | No | No | No pipes conveying liquids, gases, or vapors shall be located in the hoistway. The copper pipe in the overhead shall be removed. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | (A-16) - The wireway feeding the car and counterweight buffer switches has rusted away and has energized wires exposed. It shall be replaced. | 8/25/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The car and counterweight buffer switches shall be operational. | 8/25/2021 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | A hoist rope tag shall be provided. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction. The large hole through the back hoistway wall in the pit looking into a restroom shall be repaired. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water and oil shall not be allowed to accumulate on pit floors. Note: The pit has at least 1 foot of standing water in it. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | No | No | No pipes conveying liquids, gases, or vapors shall be located in the hoistway. The copper pipe in the overhead shall be removed. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | (A-16) - The wireway feeding the car and counterweight buffer switches has rusted away and has energized wires exposed. It shall be replaced. | 3/9/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The car and counterweight buffer switches shall be operational. | 3/9/2023 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | A hoist rope tag shall be provided. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction. The large hole through the back hoistway wall in the pit looking into a restroom shall be repaired. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Needs annual test completed after cleaning and removing rust from pistons. Re-inspection required | 10/2/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | Yes | Yes | Repair or replace defective car and counterweight buffers. Red-tagged, Re-inspection required |