Inspection
Inspection Details
Equipment ID
10718
10718
Inspection Date
2/5/2026
2/5/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James VanZant
James VanZant
Mechanic Name
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
14/12
14/12
External ID
621d310a-632e-4683-af91-4a16499792f6
621d310a-632e-4683-af91-4a16499792f6
Location
CMC Auditorium
1900 Grand Ave, Carthage, MO
Phone: (417) 358-7787
1900 Grand Ave, Carthage, MO
Phone: (417) 358-7787
Owner
Attn: Congregation of the Mother of Coredemptrix
Congregation of the Mother of Coredemptrix
1900 Grand Ave, Carthage, MO 64836
Phone: (417) 358-7787
Email: quanlycmc@gmail.com
Congregation of the Mother of Coredemptrix
1900 Grand Ave, Carthage, MO 64836
Phone: (417) 358-7787
Email: quanlycmc@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | all non elevator items must be removed from machine room | 9/1/2022 |
| conversion | conversion | n/a | No | No | needs current certificate posted in frame in machine room | 9/1/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current state certificate posted in machine room | 9/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 8.6.1.6.5 fire extinguisher hasn't been checked since 2014 | 9/1/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | all non elevator items need to be removed from machine room | 9/1/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | needs current certificate posted | 9/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Cab forced ventilation fan shall work | 9/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Car Gate switch shall not register “closed” at greater than 2” open. (REINSPECTION REQUIRED) | 4/12/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired) | 9/1/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Non-elevator related items shall not be stored in Machine Room. (vacuums, signs, etc) | 9/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Car Gate switch shall not register “closed” at greater than 2” open. (REINSPECTION REQUIRED) | 4/12/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 2021&2022: G(1)/1.14.1/1001.2(a)(14) Cab forced ventilation fan shall work (very noisy, repair or replace) | 9/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace missing "Do not use elevator in case of fire" Signage on multiple floors | 9/1/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Non-elevator related items shall not be stored in Machine Room. (Shiny wrapped boxes, dog kennel, etc.) This room is for the elevator ONLY. | 9/1/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Provide operational telephone in elevator cab | 5/1/2023 |