Inspection
Inspection Details
Equipment ID
7156
7156
Inspection Date
1/16/2019
1/16/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
26
26
External ID
3b793278-320f-4b2f-bf6a-4441dd51cc03
3b793278-320f-4b2f-bf6a-4441dd51cc03
Location
HoteLumiere
901 N 1ST ST, SAINT LOUIS, MO
901 N 1ST ST, SAINT LOUIS, MO
Owner
Attn: UNK
Pinnacle Entertainment
3800 HOWARD HUGHES PKWY, LAS VEGAS, NV 89169
Phone: (000) 000-0000
Pinnacle Entertainment
3800 HOWARD HUGHES PKWY, LAS VEGAS, NV 89169
Phone: (000) 000-0000
Billing
Attn: HoteLumiere
HoteLumiere
901 N 1ST ST, SAINT LOUIS, MO 63102
Phone: (314) 881-7870
Email: Maiazzi@lumiereplace.com
HoteLumiere
901 N 1ST ST, SAINT LOUIS, MO 63102
Phone: (314) 881-7870
Email: Maiazzi@lumiereplace.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lights need repair. Need lighting in front of #4 controller where there is none. 10 ft candle minimum. | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door needs to be self closing and locking. | 11/26/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone not working on battery power. | 12/12/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Clean oil off of floor. | 11/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated cert in machine room. | 11/26/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Suspension means, diameter loss due to wear exceeds retirement criteria. | 5/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency light, phone and alarm bell shall work. | 5/1/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lights need repair. 10 ft candle minimum | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door needs to be self closing and locking | 11/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display state operating certificate in the machine room | 11/26/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. REINSPECT REQUIRED | 4/19/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | Door closing force is to high | 11/26/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work with power off. Re-inspection required | 12/20/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self locking / self closing | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting inadequate | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired, needs serviced or replaced | 1/23/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 6/11/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | Fire extinguisher is out of date. | 11/26/2025 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.18.3 | Yes | No | Governor shall be sealed | 11/26/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Vent shaft at top of HW has a ledge greater than 4". Shall be beveled or screened to remove ledge. 2.1.6.2 | 11/26/2025 |