Inspection
Inspection Details
Equipment ID
18911
18911
Inspection Date
1/22/2019
1/22/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
b0cddc69-39b2-479c-9983-27d141afd6cf
b0cddc69-39b2-479c-9983-27d141afd6cf
Location
Lumiere Place Casino
999 N 2ND ST, SAINT LOUIS, MO
999 N 2ND ST, SAINT LOUIS, MO
Owner
Attn: Dwight Buchannon
Four Seasons Hotel
999 N 2ND ST, SAINT LOUIS, MO 63102
Phone: (314) 498-8304
Email: dwight.buchannon@fourseasons.com
Four Seasons Hotel
999 N 2ND ST, SAINT LOUIS, MO 63102
Phone: (314) 498-8304
Email: dwight.buchannon@fourseasons.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Clean and lubricate skirts to lower index value, left side. | |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 1206.6a | No | No | Demarcation lights on both ends are out. | |
| A17.1-1996 : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Certificate | No | No | Need updated cert displayed in machine room. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.3 Step/Skirt Performance Index | Yes | No | Provide testing. | 5/9/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Upper lights not working. | 5/9/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Lower lights not working. | 5/9/2023 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current State Elevator Certificate. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.11 - Skirt obstruction device | 6.1.6.3.6 | Yes | No | Upper left skirt switch is not working. | 5/9/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.4 - Drive machine and brake | 8.6.8.12 Brake | Yes | No | Provide testing of brake torque. | 5/9/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.3 Step/Skirt Performance Index | Yes | No | Testing was performed, unit failed. Repair as needed. | 8/29/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Upper lights are not working. | 8/29/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Lower lights are not working. | 8/29/2023 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current Certificate. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.4 - Drive machine and brake | 8.6.8.12 Brake | Yes | No | Provide brake torque test, record results. | 8/29/2023 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 6.1.7 | No | No | Repair switch / electrical box with exposed wiring in lower pit | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | No | No | Right side handrail stalls about every 2-3 seconds causing the handrail speed sensor to actuate. This could result in stoppage of the escalator. Repair what is causing issue |