Inspection
Inspection Details
Equipment ID
18773
18773
Inspection Date
1/23/2019
1/23/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
550
550
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
7bffe09f-5dd6-44a0-b46e-3326853eebc3
7bffe09f-5dd6-44a0-b46e-3326853eebc3
Location
Lumiere Place Casino
999 N 2ND ST, SAINT LOUIS, MO
999 N 2ND ST, SAINT LOUIS, MO
Owner
Attn: Dwight Buchannon
Four Seasons Hotel
999 N 2ND ST, SAINT LOUIS, MO 63102
Phone: (314) 498-8304
Email: dwight.buchannon@fourseasons.com
Four Seasons Hotel
999 N 2ND ST, SAINT LOUIS, MO 63102
Phone: (314) 498-8304
Email: dwight.buchannon@fourseasons.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Re-in | 12/7/2025 |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 1001.2(d)(2) | No | No | Reinstall non vision wings on hall doors. | 12/7/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated certificate in machine room. | 12/7/2025 |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 110 | No | No | The door space/site guards are missing on the bottom and top landing hoistway doors. Reinstall guards to meet code requirements. | 12/7/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 12/7/2025 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | A light fixture in the machine room was not operational, repair fixture to provide adequate lighting for maintenance and emergency personnel. | 12/7/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The fireman’s emergency service phase II operation signage is missing inside the elevator cab, reinstall signage for emergency personnel. | 12/7/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 1/2/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 12/7/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The cab ceiling is of the open egg crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve of some other means to properly protect passengers | 12/7/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Need to adjust fascia for car door restrictor to work. Re-inspection required | 12/7/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car shall work. Re-inspection required | 12/4/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room |